3: I
NSTALLATION
AND
W
IRING
3-8
FC5A M
ICRO
S
MART
U
SER
’
S
M
ANUAL
FC9Y-B1268
Mounting on DIN Rail
Caution
Install the MicroSmart modules according to instructions described in this user’s manual. Improper
installation will result in falling, failure, or malfunction of the MicroSmart.
Mount the MicroSmart modules on a 35-mm-wide DIN rail or a panel surface.
Applicable DIN rail: IDEC’s BAA1000PN10 or BAP1000PN10 (1000mm/39.4” long)
Groove
35-mm-wide DIN Rail
Clamp
1.
Fasten the DIN rail to a panel using screws firmly.
2.
Pull out the clamp from each MicroSmart module, and
put the groove of the module on the DIN rail. Press the
modules towards the DIN rail and push in the clamps as
shown on the right.
3.
Use BNL6 end clips on both sides of the MicroSmart
modules to prevent moving sideways.
Removing from DIN Rail
35-mm-wide DIN Rail
Clamp
1.
Insert a flat screwdriver into the slot in the clamp.
2.
Pull out the clamps from the modules.
3.
Turn the MicroSmart modules bottom out.
Direct Mounting on Panel Surface
MicroSmart modules can also be mounted on a panel
surface inside a console. When mounting a slim type
CPU module, digital I/O module, analog I/O module,
HMI base module, or communication module, use
optional direct mounting strip FC4A-PSP1P as described
below.
Installing the Direct Mounting Strip
(A)
(B)
Direct Mounting Strip
FC4A-PSP1P
1.
Remove the clamp from the module by pushing the
clamp inward.
2.
Insert the direct mounting strip into the slot where the
clamp has been removed (A). Further insert the direct
mounting strip until the hook enters into the recess in
the module (B).
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]