Stop Input and Reset Input
As described on page 4-5, the MicroSmart can be started and stopped using a stop input or reset input, which can be des-
ignated from the Function Area Settings menu. When the designated stop or reset input is turned on, the MicroSmart
stops operation. For the system statuses in the stop and reset modes, see page 4-6.
Since these settings relate to the user program, the user program must be downloaded to the MicroSmart after changing
any of these settings.
Programming WindLDR
1.
From the WindLDR menu bar, select
Configuration
>
Run/Stop Control
.
The Function Area Settings dialog box for Run/Stop Control appears.
2.
Click the check box under the Stop and Reset Inputs.
Stop Input:
Click the check box on the left of Use Stop Input and type a desired input number available on the CPU module
in the Stop Input field.
Reset Input:
Click the check box on the left of Use Reset Input and type a desired reset number available on the CPU module
in the Reset Input field.
This example designates
input I0 as a stop input and
input I1 as a reset input.
Resets all Function Area Set-
tings values to defaults.
Default:
No stop and reset inputs are designated.
3.
Click the
OK
button.