6: D
EVICE
A
DDRESSES
6-16
FC5A M
ICRO
S
MART
U
SER
’
S
M
ANUAL
FC9Y-B1268
M8130-M8137 Special Internal Relays for High-speed Counter
See page 5-7 and after.
M8140, M8141, M8142, M8143 Interrupt Input Status
When interrupt inputs I2 through I5 are enabled, M8140 through M8143 are turned on, respectively. When disabled,
these internal relays are turned off.
M8144 Timer Interrupt Status
When timer interrupt is enabled, M8144 is turned on. When disabled, M8144 is turned off.
M8145, M8146, M8147 User Communication Receive Instruction Cancel Flag (Port 4, Port 5, Port 6)
When M8145, M8146, or M8147 is turned on, all RXD4, RXD5, or RXD6 instructions ready for receiving user communica-
tion through port 4, port 5, or port 6 are disabled, respectively.
M8150 Comparison Result Greater Than
When the CMP= instruction is used, M8150 is turned on when the value of device designated by S1 is greater than that of
device designated by S2 (S1 > S2). See page 4-2 (Advanced Vol.).
When the ICMP>= instruction is used, M8150 is turned on when the value of device designated by S2 is greater than that
of device designated by S1 (S2 < S1). See page 4-6 (Advanced Vol.).
M8151 Comparison Result Equal To
When the CMP= instruction is used, M8151 is turned on when the value of device designated by S1 is equal to that of
device designated by S2 (S1 = S2). See page 4-2 (Advanced Vol.).
When the ICMP>= instruction is used, M8151 is turned on when the value of device designated by S3 is greater than that
of device designated by S2 (S3 > S2). See page 4-6 (Advanced Vol.).
M8152 Comparison Result Less Than
When the CMP= instruction is used, M8152 is turned on when the value of device designated by S1 is less than that of
device designated by S2 (S1 < S2). See page 4-2 (Advanced Vol.).
When the ICMP>= instruction is used, M8152 is turned on when the value of device designated by S2 is less than that of
device designated by S1 and greater than that of device designated by S3 (S1 > S2 > S3). See page 4-6 (Advanced Vol.).
M8154, M8155, M8156, M8157 Catch Input ON/OFF Status
When a rising or falling input edge is detected during a scan, the input statuses of catch inputs I2 through I5 at the
moment are set to M8154 through M8157, respectively, without regard to the scan status. Only one edge is detected in
one scan. For the catch input function, see page 5-32.
M8161-M8164 Special Internal Relays for High-speed Counter
See page 5-7 and after.
M8170 User Communication Receive Instruction Cancel Flag (Port 7)
When M8170 is turned on, all RXD7 instructions ready for receiving user communication through port 7 are disabled.
M8171 User Communication Receive over Ethernet Instruction Cancel Flag (Client Connection 1)
When M8171 is turned on, all ERXD C1 instructions ready for receiving user communication through client connection 1
are disabled.
M8172 User Communication Receive over Ethernet Instruction Cancel Flag (Client Connection 2)
When M8172 is turned on, all ERXD C2 instructions ready for receiving user communication through client connection 2
are disabled.
M8173 User Communication Receive over Ethernet Instruction Cancel Flag (Client Connection 3)
When M8173 is turned on, all ERXD C3 instructions ready for receiving user communication through client connection 3
are disabled.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]