![IDEC FS1A-C11S Скачать руководство пользователя страница 53](http://html.mh-extra.com/html/idec/fs1a-c11s/fs1a-c11s_user-manual_617376053.webp)
LOGIC
5-5
C
h
a
p
te
r 5
Wiring example of a SafetyOne and a SafetyOne
Y0
X0
X1
T0
T1
Y
1
Control category 4
MTTF
d
100 years
DC high
PL e
SafetyOne
1
SafetyOne
2
Dual Channel Safety
Y0
X0
X1
T0
T1
note:
Stopping the whole system by the safety output of
SafetyOne 1 is recommended.
(In case of a short circuit between Y0 and external
conductors, only SafetyOne 1 detects the error.)
Y
1
Control category 3
MTTF
d
100 years
DC Medium
PL d
SafetyOne
1
SafetyOne
2
Dual Channel Safety
Note:
To avoid short circuit between each cable,
-Fix the cables permanently and protect against external
damage, e.g. by cable ducting, conduit.....
or
-Use individually shielded cables with earth connection.
Warning
Applicable safety performance depends on the whole system configuration.
Содержание FS1A-C11S
Страница 1: ...FS9Z B1218 FS1A C11S Safety Controller SafetyOne User s manual ...
Страница 2: ......
Страница 10: ......
Страница 16: ...PRODUCT SPECIFICATIONS 2 4 Dimensions Detail of locking ring Locking ring ...
Страница 38: ...INSTALLATION AND WIRING 3 8 ...
Страница 48: ...BASIC OPERATIONS 4 10 ...
Страница 78: ...LOGIC 5 30 ...
Страница 90: ...LOGIC 5 42 ...
Страница 102: ...LOGIC 5 54 ...
Страница 116: ...LOGIC 5 68 ...
Страница 154: ...LOGIC 5 106 ...
Страница 231: ...LOGIC 5 183 Chapter 5 ...
Страница 307: ...LOGIC 5 259 Chapter 5 ...
Страница 319: ...LOGIC 5 271 Chapter 5 ...
Страница 331: ...LOGIC 5 283 Chapter 5 ...
Страница 386: ...LOGIC 5 338 ...