BASIC OPERATIONS
4-8
Canceling the Protection state
SafetyOne transitions to the Protection state if a failure is detected in an external device or an
error is detected in external wiring, such as when different operations are performed between
dual channel inputs or two muting inputs, when the EDM input is OFF while the safety outputs
are transitioning from OFF to ON or the EDM input is ON while the safety outputs are
transitioning from ON to OFF by output control. In the Protection state, the safety outputs are
turned OFF and "1" is displayed in the error LED display. The Protection state can be cancelled
by the following methods.
Cancellation by the connected control devices
In case of an error with the dual channel input, the Protection state is cancelled by turning OFF
the appropriate dual channel input. (For example: Press an emergency stop switch or open a
guard equipped with an interlock device.) But cancellation is not achieved during OFF-delay
operation of safety outputs.
In case of an error with muting input, the Protection state is cancelled by turning OFF of the
appropriate muting input. But cancellation is not achieved during OFF-delay operation of safety
outputs.
In case of an error with mode select input, the Protection state is cancelled by turning OFF 1 of
the appropriate 2 inputs. But the cancellation is not achieved during OFF-delay operation of
safety outputs.
In case of an error with the EDM input, the Protection state is cancelled by turning ON the
appropriate EDM input. When an EDM input causes an error, the corresponded safety output is
not turned ON, but the other safety output can be turned ON and after approximately 1s turned
OFF. For the relationship between EDM inputs and safety outputs, refer Table 4.3 shown below.
Table 4.3 EDM inputs and corresponded safety outputs
Safety output types
EDM inputs
(External Device Monitor inputs)
Safety outputs
Dual channel outputs
T14-X14
Y0, Y1
T15-X15
Y2, Y3
Single channel outputs
T12-X12
Y0
T13-X13
Y1
T14-X14
Y2
T15-X15
Y3
Cancellation by resetting power to SafetyOne
The Protection state is cancelled by restarting power to SafetyOne after removing the error
factor.
If the error factor that caused the change to the Protection state has been not removed, the unit
returns to the Protection state again.
Cancellation by transition to Protection state
By the changing the configuration of a logic or timer switch, the state changes from Protection
state to Configuration state.
Содержание FS1A-C11S
Страница 1: ...FS9Z B1218 FS1A C11S Safety Controller SafetyOne User s manual ...
Страница 2: ......
Страница 10: ......
Страница 16: ...PRODUCT SPECIFICATIONS 2 4 Dimensions Detail of locking ring Locking ring ...
Страница 38: ...INSTALLATION AND WIRING 3 8 ...
Страница 48: ...BASIC OPERATIONS 4 10 ...
Страница 78: ...LOGIC 5 30 ...
Страница 90: ...LOGIC 5 42 ...
Страница 102: ...LOGIC 5 54 ...
Страница 116: ...LOGIC 5 68 ...
Страница 154: ...LOGIC 5 106 ...
Страница 231: ...LOGIC 5 183 Chapter 5 ...
Страница 307: ...LOGIC 5 259 Chapter 5 ...
Страница 319: ...LOGIC 5 271 Chapter 5 ...
Страница 331: ...LOGIC 5 283 Chapter 5 ...
Страница 386: ...LOGIC 5 338 ...