LOGIC
5-130
Timing chart (Logic 12d)
Example: Manual start input (X12) is used.
Min. 0.1s
Safety output 2:
Y2, Y3
Monitor output for
Safety output 2: Y13
Safety output 1:
Y0, Y1
Monitor output for
Safety output 1: Y12
Safety input 2: X2
Start input 1: X12
(Manual)
Monitor output for
safety input 2: Y5
State monitor output 3:
Y16
Logic function monitor
output 2: Y20
Safety input 2: X3
Max. 6s
Initialization
note 1)
note 1)
Logic function monitor
output 1: Y17
Control input 1: X16
Control input 2: X17
Power
ON
Safety
output
1
ON
Safety
output
2
ON
Max. 0.1s
OFF delay time
OFF delay time
Safety
output
1
ON
Safety
output
2
ON
Safety
output
1
ON
Safety
output
2
ON
(Safety input 1, 3, 4 and 5 are all ON in this chart.)
Note 1) Input monitor error detection time is infinity.
About safety inputs that are not described in this chart, input monitor error detection time is as follows.
The time of dual channel direct opening input (X0, X1) is 0,5s.
The time of dual channel dependent input (X4 to X7) is infinity.
The time of dual channel safety input (X10, X11) is 0,1s.
Refer to the following “Logic functions” for more details.
Содержание FS1A-C11S
Страница 1: ...FS9Z B1218 FS1A C11S Safety Controller SafetyOne User s manual ...
Страница 2: ......
Страница 10: ......
Страница 16: ...PRODUCT SPECIFICATIONS 2 4 Dimensions Detail of locking ring Locking ring ...
Страница 38: ...INSTALLATION AND WIRING 3 8 ...
Страница 48: ...BASIC OPERATIONS 4 10 ...
Страница 78: ...LOGIC 5 30 ...
Страница 90: ...LOGIC 5 42 ...
Страница 102: ...LOGIC 5 54 ...
Страница 116: ...LOGIC 5 68 ...
Страница 154: ...LOGIC 5 106 ...
Страница 231: ...LOGIC 5 183 Chapter 5 ...
Страница 307: ...LOGIC 5 259 Chapter 5 ...
Страница 319: ...LOGIC 5 271 Chapter 5 ...
Страница 331: ...LOGIC 5 283 Chapter 5 ...
Страница 386: ...LOGIC 5 338 ...