LOGIC
5-58
●Muting inputs: X2, X3, X6, and X7
Muting inputs are used to diagnose the status of muting devices, such as sensors or limit switches.
Intended inputs
(Terminal names)
Target safety
inputs
(Terminal
names)
Function
Muting input 1
(X2, X3)
Safety input 1
(X0, X1)
Function name
Muting input+Muting II
Muting input 2
(X6, X7)
Safety input 2
(X4, X5)
Symbol
Muting input
+
Muting
function
Ⅱ
Safety
input
Muting
( ∞)
Description of
operation
This function diagnoses the status of connected
muting devices. This function diagnoses the time
interval of status transition between each input of
duplicated inputs (3s). The function does not use
a drive terminal (T2, T3, T6, T7).
Detail
information
Logic functions (5-323, 329)
Warning
Muting inputs are not safety inputs. Do not use these to construct a safety system.
The maximum time to suspend the safety function continuously (muting monitor time) is not specified
in the SafetyOne. Based on risk assessment, monitor the muting monitor time that is suitable for the
safety system, by external circuit or devices.
Содержание FS1A-C11S
Страница 1: ...FS9Z B1218 FS1A C11S Safety Controller SafetyOne User s manual ...
Страница 2: ......
Страница 10: ......
Страница 16: ...PRODUCT SPECIFICATIONS 2 4 Dimensions Detail of locking ring Locking ring ...
Страница 38: ...INSTALLATION AND WIRING 3 8 ...
Страница 48: ...BASIC OPERATIONS 4 10 ...
Страница 78: ...LOGIC 5 30 ...
Страница 90: ...LOGIC 5 42 ...
Страница 102: ...LOGIC 5 54 ...
Страница 116: ...LOGIC 5 68 ...
Страница 154: ...LOGIC 5 106 ...
Страница 231: ...LOGIC 5 183 Chapter 5 ...
Страница 307: ...LOGIC 5 259 Chapter 5 ...
Страница 319: ...LOGIC 5 271 Chapter 5 ...
Страница 331: ...LOGIC 5 283 Chapter 5 ...
Страница 386: ...LOGIC 5 338 ...