![IDEC FS1A-C11S Скачать руководство пользователя страница 157](http://html.mh-extra.com/html/idec/fs1a-c11s/fs1a-c11s_user-manual_617376157.webp)
LOGIC
5-109
C
h
a
p
te
r 5
Functions (Logic 12C)
●Safety inputs: X0 to X13 (T0, T1, T4, T5, and T10 to T13)
Safety inputs are used to diagnose the status of connected safety devices, such as emergency stop
switches.
Intended inputs
(Terminal names)
Function
Safety input 1
(X0-T0, X1-T1)
Safety input 3
(X4-T4, X5-T5)
Safety input 5
(X10-T10, X11-T11)
Safety input 6
(X12-T12, X13-T13)
Function name
Dual channel direct opening input
Symbol
Dual Channel
Direct Opening
Description of operation
This function diagnoses the status of
connected safety devices. This function
diagnoses the time interval of status
transition between each input of
duplicated inputs (0.5s).
Detail information
Logic functions (5-311)
Intended inputs
(Terminal names)
Function
Safety input 2
(X2, X3)
Safety input 4
(X6, X7)
Function name
Dual channel safety input
Symbol
Dual Channel Safety
Description of operation
This function diagnoses the status of
connected safety devices. This function
diagnoses the time interval of status
transition between each input of
duplicated inputs (0.1s). The function
does not use drive terminals (T2, T3, T6
and T7).
Detail information
Logic functions (5-317)
Содержание FS1A-C11S
Страница 1: ...FS9Z B1218 FS1A C11S Safety Controller SafetyOne User s manual ...
Страница 2: ......
Страница 10: ......
Страница 16: ...PRODUCT SPECIFICATIONS 2 4 Dimensions Detail of locking ring Locking ring ...
Страница 38: ...INSTALLATION AND WIRING 3 8 ...
Страница 48: ...BASIC OPERATIONS 4 10 ...
Страница 78: ...LOGIC 5 30 ...
Страница 90: ...LOGIC 5 42 ...
Страница 102: ...LOGIC 5 54 ...
Страница 116: ...LOGIC 5 68 ...
Страница 154: ...LOGIC 5 106 ...
Страница 231: ...LOGIC 5 183 Chapter 5 ...
Страница 307: ...LOGIC 5 259 Chapter 5 ...
Страница 319: ...LOGIC 5 271 Chapter 5 ...
Страница 331: ...LOGIC 5 283 Chapter 5 ...
Страница 386: ...LOGIC 5 338 ...