LOGIC
5-253
C
h
a
p
te
r 5
●Safety input monitor outputs: Y4 to Y10
Safety input monitor outputs are used to output the status of safety inputs in SafetyOne.
Intended outputs
(Terminal names)
Target safety inputs
(Terminal names)
Description of operation
Safety input 1 monitor output
(Y4)
Safety input 1
(X0-T0: TEACH)
When TEACH mode (X0) is selected,
the monitor output is ON. When
TEACH mode is not selected, the
monitor output is OFF.
Safety input 2 monitor output
(Y5)
Safety input 2
(X2-T2, X3-T3)
When the target safety input is ON,
the monitor output is ON. When the
target safety input is OFF, the monitor
output is OFF.
Safety input 3 monitor output
(Y6)
Safety input 3
(X4-T4, X5-T5)
Safety input 4 monitor output
(Y7)
Safety input 4
(X6-T6, X7-T7)
Safety input 5 monitor output
(Y10)
Safety input 5
(X10, X11)
Note. When the targeted safety input detects an input monitor error, input circuit failure, or EMC the
disturbance, corresponding safety input monitor output becomes a pulse output (1Hz). The
monitor output is OFF in other errors, Initial state, or Configuration state.
●Safety output monitor outputs: Y12, Y13, Y17, and Y20
Safety output monitor outputs are used to output status of safety outputs in SafetyOne.
Intended outputs
(Terminal names)
Target safety outputs
(Terminal names)
Description of operation
Safety output 1 monitor output
(Y12)
Safety output 1
(Y0)
When the target safety output is ON,
the monitor output is ON. When the
target safety output is OFF, this
function is OFF. The monitor output
turns OFF immediately, independent
of the preset OFF-delay time.
Safety output 2 monitor output
(Y13)
Safety output 2
(Y1)
Safety output 3-1 monitor output
(Y17)
Safety output 3-1
(Y2)
Safety output 3-2 monitor output
(Y20)
Safety output 3-2
(Y3)
Note. When the safety output detects an output circuit failure, corresponding safety output monitor
output becomes a pulse outputs (1Hz). The monitor output is OFF in other errors, Initial state, or
Configuration state.
Содержание FS1A-C11S
Страница 1: ...FS9Z B1218 FS1A C11S Safety Controller SafetyOne User s manual ...
Страница 2: ......
Страница 10: ......
Страница 16: ...PRODUCT SPECIFICATIONS 2 4 Dimensions Detail of locking ring Locking ring ...
Страница 38: ...INSTALLATION AND WIRING 3 8 ...
Страница 48: ...BASIC OPERATIONS 4 10 ...
Страница 78: ...LOGIC 5 30 ...
Страница 90: ...LOGIC 5 42 ...
Страница 102: ...LOGIC 5 54 ...
Страница 116: ...LOGIC 5 68 ...
Страница 154: ...LOGIC 5 106 ...
Страница 231: ...LOGIC 5 183 Chapter 5 ...
Страница 307: ...LOGIC 5 259 Chapter 5 ...
Страница 319: ...LOGIC 5 271 Chapter 5 ...
Страница 331: ...LOGIC 5 283 Chapter 5 ...
Страница 386: ...LOGIC 5 338 ...