Chapter4 BASIC OPERATIONS
This chapter describes the basic operations of SafetyOne. Make proper use of the
SafetyOne by thoroughly familiarizing yourself with basic operations and functions.
Internal states
The SafetyOne operates in five internal states, as shown in Table 4.1.
The LED display and output status for each state are shown in Table 4.2.1and 4.2.2.
Table 4.1 Internal states
State
Description
Initial
Initial processing is performed immediately after power is supplied to the SafetyOne.
The internal circuits are checked and the LEDs show operation confirmation (blinking)
for 6 seconds (approx)..
Run
The SafetyOne is under normal operation. Logic processing continues without failures
or wiring errors. (Refer to "Chapter 5 LOGIC" for details.)
Configuration
A logic or OFF-delay timer value is being configured.
Configuration enables the logic and OFF-delay timer value. When completed, the
SafetyOne changes to the Run state. (Refer to "Logic configuration" and "Timer
configuration" in this chapter for details.)
Protection
An input monitor error has occurred with dual channel input, EDM input, or muting
input. When the problem is removed, the SafetyOne changes to Run state. (Refer to
"Canceling the Protection state" in this chapter for details.)
Stop
A failure or error has occurred with an external device or internal circuit. When the
problem is removed and the power is turned on, Stop state is cleared. (Refer to
"Canceling the Stop state" in this chapter for details.)
Table 4.2.1 LED display and output status for each state
(When safety outputs are dual channel outputs)
State
Logic
LED
Error
LED
Timer
LED
Safety
output
Solenoid/
lamp output
Monitor output
Y0…Y3
Y17,Y20
Y4…Y13
Y14
Y15
Y16
Initial
(1)
(1)
(1)
□
OFF
□
OFF
□
OFF
■
ON
■
ON
□
OFF
Run
Logic #
Blank
Selected Value
(2)
(2)
(2)
□
OFF
□
OFF
■
ON
Configuration
(3)
“C”
(3)
□
OFF
□
OFF
□
OFF
□
OFF
■
ON
□
OFF
Protection
Logic #
“1”
Selected Value
□
OFF
(6)
□
OFF
(4)
□
OFF
■
ON
□
OFF
Stop
Blank
(5)
Blank
□
OFF
□
OFF
(4)
■
ON
■
ON
or
□
OFF
□
OFF
Table 4.2.2 LED display and output status for each state
(When safety outputs are single channel outputs)
State
Logic
LED
Error
LED
Timer
LED
Safety
output
Monitor output
Y0…Y3
Y4…Y13, Y17, Y20
Y14
Y15
Y16
Initial
(1)
(1)
(1)
□
OFF
□
OFF
■
ON
■
ON
□
OFF
Run
Logic #
Blank
Selected Value
(2)
(2)
□
OFF
□
OFF
■
ON
Configuration
(3)
“C”
(3)
□
OFF
□
OFF
□
OFF
■
ON
□
OFF
Protection
Logic #
“1”
Selected Value
□
OFF
(6)
(4)
□
OFF
■
ON
□
OFF
Stop
Blank
(5)
Blank
□
OFF
(4)
■
ON
■
ON
or
□
OFF
□
OFF
Содержание FS1A-C11S
Страница 1: ...FS9Z B1218 FS1A C11S Safety Controller SafetyOne User s manual ...
Страница 2: ......
Страница 10: ......
Страница 16: ...PRODUCT SPECIFICATIONS 2 4 Dimensions Detail of locking ring Locking ring ...
Страница 38: ...INSTALLATION AND WIRING 3 8 ...
Страница 48: ...BASIC OPERATIONS 4 10 ...
Страница 78: ...LOGIC 5 30 ...
Страница 90: ...LOGIC 5 42 ...
Страница 102: ...LOGIC 5 54 ...
Страница 116: ...LOGIC 5 68 ...
Страница 154: ...LOGIC 5 106 ...
Страница 231: ...LOGIC 5 183 Chapter 5 ...
Страница 307: ...LOGIC 5 259 Chapter 5 ...
Страница 319: ...LOGIC 5 271 Chapter 5 ...
Страница 331: ...LOGIC 5 283 Chapter 5 ...
Страница 386: ...LOGIC 5 338 ...