Check that the default system output voltage and current limit match the
requirements of the battery and the loads to be connected.
Mount the unit in an enclosed standard 19 inch equipment rack or other
restricted access location, using rack mounting screws (not supplied). Support the
rear of the unit with rack supports or back rail if required.
Make connections to the load using wire and connectors appropriately rated for
the maximum output current capability of the unit. The load may be powered
three different ways:
Load Connection Point
Features
Directly from main system DC Output
Bus Bars
Full current rating of the system is
available to operate the load, limited
only by the maximum output
capability of the combined Power
Modules
One of up to twelve LDM Intelligent
Output Channel Connector Ports
Channel over current protection with
LDM front circuit breaker (1 to 12),
individual remote channel on/off
control and current monitoring
High Current BMMD Output Bus Bar
Output over current protection with
BMMD dual 100A load breakers
The
LDM
outputs have
Output
and
Return
connection provided for each
channel. Verify supply polarity before connecting loads.
Connect a ground bonding wire from the chassis rear ground stud to the rack.
Make Sensor and Alarm Connections
•
Connect the form-C alarm contact monitoring wiring to the ALARM Output
connector if needed, as shown in the following table. The top master
system contacts are flagged for all system alarms while the lower level
contacts indicate power module faults only for the lower shelf.