INSTRUCTION MANUAL 

855-340-032 

Innovative Circuit 

Technology Ltd. 

DC Power System Models: 

ICT-2U4 
ICT-2U5 
ICT-2U6 
ICT-2U8 

Содержание ICT-2U4

Страница 1: ...MPS Ultra DC Power System INSTRUCTION MANUAL 855 340 032 Innovative Circuit Technology Ltd DC Power System Models ICT 2U4 ICT 2U5 ICT 2U6 ICT 2U8...

Страница 2: ...d current and size of battery fuse or circuit breaker Ensure battery polarity is correct before connecting Do not attempt to charge a frozen battery Handle batteries with care never short circuit batt...

Страница 3: ...nd Advanced Options 22 Password Reset Front panel 22 OPERATION Network GUI 23 Log In to the Unit 23 System 24 Power Modules 25 Battery Backup with optional Battery Management Module 26 Load Distributi...

Страница 4: ...KW models include battery state of charge estimated run time remaining and battery discharge testing Power Module Ratings Power Modules must be ordered separately Module 12V 50A ICT700 12 24V 25A ICT7...

Страница 5: ...larm relay connectors installed Plastic U shaped cover with four 6 32x1 4 screws for output bus bars in bag Four bolt washer nut sets for connections to the bus bars in bag Remote battery temperature...

Страница 6: ...W of output power ICT 2U8 positive or negative output Power Modules must be ordered separately Description Model No 12V 700W Power Module 13 8V 50A ICT700 12PM 24V 700W Power Module 27 6V 25A ICT700 2...

Страница 7: ...true N 1 redundant operation N 1 operation requires excess power module capacity to ensure that the load can be fully powered even if one power module should fail or be removed Carefully align each m...

Страница 8: ...ttery connection Only use the Equalize Charge setting for flooded lead acid batteries in a well ventilated location Do not use Equalize Charge on sealed batteries Always consult with battery manufactu...

Страница 9: ...e load limited only by the maximum output capability of the combined Power Modules One of up to twelve LDM Intelligent Output Channel Connector Ports Channel over current protection with LDM front cir...

Страница 10: ...this must be set according to the manufacturer s recommendation for your battery to enable charge voltage temperature compensation Battery temperature is assumed to be 25 C if no sensor is installed F...

Страница 11: ...ery to the BMMD Only use the Equalize Charge setting for flooded lead acid batteries in a well ventilated location Do not use Equalize Charge on sealed batteries Always consult with battery manufactur...

Страница 12: ...re 6 A Positive Voltage system will have the battery tied to the BMMD terminal with the battery tied to the main NEG output busbar Figure 7 Make Load Connections to LDM Up to three Load Distribution M...

Страница 13: ...ear figure 8 Figure 8 Install Parallel Control Cable Check that all connections to the power supply are correct and tight re install the plastic bus bar cover s using the screws provided Connect the A...

Страница 14: ...art up and operate at the factory default settings when AC power is connected generally requiring no other set up or adjustment for basic operation Use the front graphic display and four interface but...

Страница 15: ...using the up and down arrows the back button and the Enter button The output voltage and current limit settings apply to the combined output of all installed power modules The ICM treats the combined...

Страница 16: ...ld be adjusted to match your actual system and battery float voltage requirements as shown below Scroll to highlight the parameter to change System Voltage Max total Output Current Limit Output Enable...

Страница 17: ...status screen indicates the Battery Voltage Vdc the combined Battery Current Adc for charging Adc for discharging the approximate battery State of Charge SOC and a bar graph showing relative magnitude...

Страница 18: ...ystem can estimate the total battery SOC Also set the Battery Rate hrs used in the battery specification to determine the battery capacity Usually will be 20hr or 10hr rate Series connected batteries...

Страница 19: ...if messaging is configured via the Network GUI will indicate a Test Failure if the Stop Voltage is hit before the Max Time limit as the battery was not able to power the load for the desired duration...

Страница 20: ...ct location prior to snapping in place The LDM Status screen shows the output current for each of the four outputs plus indicates if a breaker is OPEN and if an output has been switched OFF LDM Settin...

Страница 21: ...the alarm inputs using the Network GUI interface The factory default setting has the alarm inputs disabled you must select a contact type for each input to enable it Alarm History Scroll through the...

Страница 22: ...gs and without interrupting DC power to the output terminals or Reset Comm Settings sets GUI password Communication settings and IP address to the factory defaults Note You will be prompted to enter t...

Страница 23: ...ess field of your browser as shown The default IP address of the unit is 192 168 0 180 but any MPS connected to a network with a DHCP server will be assigned a different IP address automatically To fi...

Страница 24: ...the internal alarm relay and the four remote alarm inputs Click on the SETTINGS CONTROL tab to configure all system related settings Click on the Save Settings button at the bottom of the page to stor...

Страница 25: ...x current requirement of the load and or battery Auto Restart Delay Auto Restart Delay Enter the delay time that the system output will remain disabled after the Auto Restart button is clicked The sys...

Страница 26: ...nt positive value for charging and negative value for discharging temperature if ICT TMP probe is installed Net Ah count approximate Ah discharged from the battery where 0Ah denotes full charge LVD st...

Страница 27: ...e total battery pack connected to the power system Connecting two batteries in parallel will double the total Ah capacity while connecting batteries in series will increase the voltage with no change...

Страница 28: ...disable this alarm default setting Alarm Reporting Activate Alarm Form C Contact Check this box default to have the back panel alarm contacts change state for an alarm condition Send E mail Check this...

Страница 29: ...lead acid batteries only A regular high voltage equalize charge will help prevent stratification of the electrolyte in your battery and can help extend its life Equalize Duration Enter the time durati...

Страница 30: ...more than 50 of the nominal battery capacity to avoid stressing the battery due to a deep discharge The Battery Discharge Test is only available if the system is configured for use with a lead acid t...

Страница 31: ...harge Tests Discharge test can only be initiated when the battery is fully charged If the system is unable to start a discharge test at the selected start time it will attempt again at the same time n...

Страница 32: ...le Control Module Output Control Output _ Click the On or Off button to remotely enable or disable that output channel All outputs are enabled as the factory default setting If power cycling is enable...

Страница 33: ...output channel if desired Output State after Power Loss Sets the state for an output channel after the LDM loses all input power then recovers Select one of the following Restore last State This will...

Страница 34: ...g DC bus voltage thresholds are not used and will be greyed out Load Shedding Auto Recovery Check this box to allow an output channel to be automatically reconnected when the bus voltage is above the...

Страница 35: ...NGS CONTROL tab to configure the input alarm settings Click on the Save Settings button at the bottom of the page to store your changes Alarm Input _ Alarm Name Enter a descriptive name for the select...

Страница 36: ...the bottom of the page to store your changes Power System Device Info Device Name Enter a device name for the system this will be used for all e mailed messages Model Hardware Model and hardware revis...

Страница 37: ...Output as the reset target will cause the main output to power cycle Data Logging Data Logging Select Enabled to keep a running record of all the key system parameters and alarms recorded once per mi...

Страница 38: ...with the panel HTTP Port Enter an HTTP port within the range of 1 to 65565 to be used for HTTP traffic between the panel and the browser The default HTTP port is 80 If a new HTTP port is selected the...

Страница 39: ...able SNMP Check this box to enable the SNMP agent SNMP Version Select the SNMP version v1 v2c v3 or All supported by the SNMP agent If All is selected all SNMP versions will be supported simultaneousl...

Страница 40: ...n protocol is selected enter the authentication password Privacy Protocol Select the SNMPv3 privacy protocol None or AES Privacy Password If a privacy protocol is selected enter the privacy password S...

Страница 41: ...d for this is available from your Network Administrator or Internet Service Provider ISP E mail SMTP Server Enter the name or the IP address of your SMTP server used for sending outgoing e mail e g sm...

Страница 42: ...one or more of these events occurs AC Input Power is lost Check this box to receive an e mail notification when the ac input drops below a functional level Power Module Failure occurs Check this box...

Страница 43: ...and change some of the basic settings View Only User can only view status cannot change any settings New Password Use these fields to change the password of the selected user New Password Enter the ne...

Страница 44: ...er Module Export and Import Settings The Manage Settings button will take you to the Export and Import Settings page where you may export all the system settings other than the Administrator password...

Страница 45: ...ng a Linksys WRT54G router others will be similar 1 Log into your router and go to the port forwarding screen In the example Linksys WRT54G router this is located in the Applications and Gaming tab Th...

Страница 46: ...assigned by the ISP With the example router this information is on the Status tab listed as IP Address NOTE When using a dynamic IP address the router s WAN IP address may change from time to time wit...

Страница 47: ...l phone number Cell address formats for some common North American mobile phone providers AT T cellnumber txt att net Verizon cellnumber vtext com Sprint cellnumber messaging sprintpcs com T Mobile ce...

Страница 48: ...he panel Verify that the Send E mail checkboxes are ticked for any alarm conditions for which you wish to receive e mail notifications Verify your e mail settings by going to the Communications Mainte...

Страница 49: ...ay Send Email2 Power Failure Loss of AC power to module Disabled Off Off Active Yes Module Operating Normal operation On Off On No Configuration Error Different voltage modules installed Off On Off Ac...

Страница 50: ...ition Output Relays ICM Required Alarm Relay Send Email3 Module Power Failure Loss of AC and DC bus connection Open No Yes No Alarms Normal Operation outputs enabled Closed No No Circuit Breaker Open...

Страница 51: ...r Factor 0 99 typ 120Vac input Efficiency typical 90 93 Output V Line Regulation 0 1 4 Actual Operating point may be lower due to battery charge requirement Power System 12V Module 24V Module 48V Modu...

Страница 52: ...e Temperature Range 40 to 70 C Humidity Operating 10 90 non condensing Storage 5 95 non condensing Cooling Load controlled fan on power modules Regulatory Compliance UL CSA 60950 1 UL CSA 62368 1 ICES...

Страница 53: ...e instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful i...

Страница 54: ...ipper regarding such damage Product that is returned as defective which is determined to operate within published specifications will be returned to the Purchaser freight collect ICT assigns to Purcha...