M-7084 User Manual, Rev. A1.3 7PH-013-A13
116
2.45 ~AATnn
Description:
Sets the soft INIT time out value.
Syntax:
~AATnn[CHKSUM](CR)
~
Delimiter character
AA
Address of the module to be set (00 to FF)
T
Command to set the soft INIT time out value
nn
Two hexadecimal digits representing the time out
value in seconds. The max time out value is 60
seconds. When changing the Baud Rate or
checksum settings without altering the INIT* pin,
the ~AAI and %AANNTTCCFF commands should
be sent consecutively and the time interval between
the two commands should be less than the soft INIT
time out. If the soft INIT time out is 0, then the
Baud Rate and checksum settings cannot be
changed using software only. The power on reset
value of the soft INIT time out is 0.
Содержание I-7000 Series
Страница 7: ...M 7084 User Manual Rev A1 3 7PH 013 A13 7 1 2 Terminal Assignment...
Страница 10: ...M 7084 User Manual Rev A1 3 7PH 013 A13 10 1 4 Block Diagram 1 4 1 Block Diagram for the M 7084...
Страница 24: ...M 7084 User Manual Rev A1 3 7PH 013 A13 24 1 11 2 Piggyback Mounting...
Страница 25: ...M 7084 User Manual Rev A1 3 7PH 013 A13 25 1 11 3 Wall Mounting...