M-7084 User Manual, Rev. A1.3 7PH-013-A13
117
Response:
Valid Response:
!AA[CHKSUM](CR)
Invalid Response:
?AA[CHKSUM](CR)
!
Delimiter character for a valid response
?
Delimiter character for an invalid response
AA
Address of the responding module (00 to FF)
There will be no response if the command syntax is incorrect,
there is a communication error, or there is no module with the
specified address.
Examples:
Command: ~01I
Response: !01
Sets the soft INIT of module 01 and returns a valid
response.
Command: %0101000700
Response: ?01
Attempts to change the Baud Rate of module 01 to
19200 without first altering the INIT * pin. The module
returns an invalid response because the soft INIT time
out value is 0.
Command: ~01T10
Response: !01
Sets the soft INIT time out value of module 01 to 16
seconds and returns a valid response.
Command: ~01I
Response: !01
Sets the soft INIT of module 01 and returns a valid
response.
Command: %0101000700
Response: !01
Changes the Baud Rate of module 01 to 19200 without
first altering INIT * pin. The module returns a valid
response.