M-7084 User Manual, Rev. A1.3 7PH-013-A13
121
Address
Description
Attribute
00033 ~ 00040 Input status after XOR mask for channel 0 to 7
R
00041 ~ 00048 Input status after low-pass filter for channel 0 to 7 R
00065 ~ 00072 Counter overflow status for channel 0 to 7. Write 1
to clear
R/W
00257
Protocol, 0: DCON, 1: Modbus RTU
R/W
00261
1: enable, 0: disable host watchdog
R/W
00269
Data format for frequency type, 0: hex, 1: float
R/W
00270
Host watch dog timeout status, write 1 to clear host
watch dog timeout status
R/W
00273
Reset status, 1: first read after powered on, 0: not
the first read after powered on
R
00513 ~ 00520 Write 1 to clear counter 0 ~ 7
W
00769 ~ 00776 Enable battery backup for counter 0 to 7
R/W
00801 ~ 00808 Automatic switching between high/low frequency
mode for frequency measurement of channel 0 to 7
R/W
00833 ~ 00840 High/low frequency mode for frequency
measurement of channel 0 to 7
It is recommended to set to high frequency mode
for frequency larger than 10 KHz.
R/W
00865 ~ 00872 Stop counting on counter overflow for channel 0 to
7
R/W
00897 ~ 00904 Enable low pass filter for channel 0 to 7
R/W
00929 ~ 00936 XOR mask for channel 0 to 7
R/W