M-7084 User Manual, Rev. A1.3 7PH-013-A13
59
2.15 $AA7
Description:
Reads the counter overflow status of each channel.
Syntax:
$AA7[CHKSUM](CR)
$
Delimiter character
AA
Address of the module to be read (00 to FF)
7
Command to read the counter overflow status
Response:
Valid Command:
!AAVV[CHKSUM](CR)
Invalid Command:
?AA[CHKSUM](CR)
!
Delimiter character for a valid command
?
Delimiter character for an invalid command
AA
Address of the responding module (00 to FF)
VV
A two-digit hexadecimal value, where bit 0
corresponds to channel 0, bit 1 corresponds to
channel 1, etc. For type code 50, when the bit is 1 it
means that the counter of the channel is overflowed
and 0 means that the counter of the channel is not
overflowed. For type code 54 ~ 56, the overflow
status is represented by two bits.
00: no over/underflow
01: overflow
10: underflow
11: not applicable