M-7084 User Manual, Rev. A1.3 7PH-013-A13
33
Related Commands:
Section 2.6 $AA2, Section 2.41 ~AAI, Section 2.45 ~AATnn
Related Topics:
Section 1.9 Configuration Tables, Section A.1 INIT* pin
Operation
Notes:
1.
Changes to the address and data format settings take effect
immediately after a valid command is received. Changes
to the Baud Rate and checksum settings take effect on the
next power-on reset.
2.
For the M-7084, changing the Baud Rate and checksum
settings can be achieved using software only and is
performed using the following commands:
I.
Send a ~AATnn command. See Section 2.45 for
details.
II.
Send a ~AAI command. See Section 2.41 for details.
III.
Send a %AANNTTCCFF command.
If the command is valid, the Baud Rate and checksum
settings will be changed after the module responds
with !AA.
Содержание I-7000 Series
Страница 7: ...M 7084 User Manual Rev A1 3 7PH 013 A13 7 1 2 Terminal Assignment...
Страница 10: ...M 7084 User Manual Rev A1 3 7PH 013 A13 10 1 4 Block Diagram 1 4 1 Block Diagram for the M 7084...
Страница 24: ...M 7084 User Manual Rev A1 3 7PH 013 A13 24 1 11 2 Piggyback Mounting...
Страница 25: ...M 7084 User Manual Rev A1 3 7PH 013 A13 25 1 11 3 Wall Mounting...