M-7084 User Manual, Rev. A1.3 7PH-013-A13
64
Examples:
Command: $017C0R50
Response: !01
Sets the type code for channel 0 of module 01 to be 50
(up counting) and the module returns a valid response.
Command: $037C1R30
Response: ?03
Sets the type code for channel 1 of module 03 to be 30.
The module returns an invalid response because the type
code is invalid.
Related Commands:
Section 2.18 $AA8CN
Related Topics:
Section 1.9 Configuration Tables
Note:
If the type code of a channel is set to one of 54 ~ 56, then the
adjacent channel in the same pair will be set to the same type
code.