2.31 @AAFTVV
Description:
Sets the frequency measurement time out value of a module.
Syntax:
@AAFTVV[CHKSUM](CR)
@
Delimiter character
AA
Address of the module to be read (00 to FF)
FT
Command to set the frequency measurement time
out
VV
Two hexadecimal digits to represent the timeout
value in tenths of a second, for example, 01 denotes
0.1 seconds and FF denotes 25.5 seconds.
Response:
Valid Command:
!AA[CHKSUM](CR)
Invalid Command:
?AA[CHKSUM](CR)
!
Delimiter character for a valid command
?
Delimiter character for an invalid command
AA
Address of the responding module (00 to FF)
There will be no response if the command syntax is incorrect,
there is a communication error, or there is no module with the
specified address.