M-7084 User Manual, Rev. A1.3 7PH-013-A13
32
Response:
Valid Command:
!AA[CHKSUM](CR)
Invalid Command:
?AA[CHKSUM](CR)
!
Delimiter for a valid command
?
Delimiter for an invalid command. If the
Baud Rate
or
checksum
settings are changed without connecting
the INIT* pin to ground or switching the rear slide
switch to the INIT position, the module will return an
invalid command.
AA
Address of the module in hexadecimal format (00 to
FF)
There will be no response if the command syntax is incorrect,
there is a communication error, or there is no module with the
specified address.
Examples:
Command: %0102000600
Response: !02
Changes the address of module 01 to 02. The module
returns a valid response.
Command: %0101000A00
Response: ?01
Changes the Baud Rate of module 01 to 115200bps. The
module returns an invalid command, because it is not in
INIT* mode.
Command: %0101000A00
Response: !01
Changes the Baud Rate of module 01 to 115200bps and
the module is in INIT* mode. The module returns a
valid response.