M-7084 User Manual, Rev. A1.3 7PH-013-A13
95
2.34 @AASC
Description:
Reads the stop counting on overflow status of each channel.
Syntax:
@AASC[CHKSUM](CR)
@
Delimiter character
AA
Address of the module to be read (00 to FF)
SC
Command to read the stop counting on overflow
status
Response:
Valid Command:
!AAVV[CHKSUM](CR)
Invalid Command:
?AA[CHKSUM](CR)
!
Delimiter character for a valid command
?
Delimiter character for an invalid command
AA
Address of the responding module (00 to FF)
VV
A two-digit hexadecimal value, where bit 0
corresponds to channel 0, bit 1 corresponds to
channel 1, etc. When the bit is 1 it means that the
stop counting on overflow is enabled for the
channel and 0 means that the stop counting on
overflow is disabled for the channel.
There will be no response if the command syntax is incorrect,
there is a communication error, or there is no module with the
specified address.