21
1.10.2 INIT Mode
When the module is powered on, with the rear slide switch set
to the INIT position as shown in the figure below for modules
with frame ground, or with the INIT* pin connected to the
GND pin for modules without frame ground, the module is in
INIT mode, (see Section A.1 for details), and the
communication settings are as follows:
1.
Address: 00
2.
Baud Rate: 9600 bps
3.
No checksum
4.
Protocol: DCON
If communication with the module is not possible, set the
module to the INIT mode and use the above settings to
communicate with the module. To read the current settings,
send the commands $AA2, (see Section 2.6), and $AAP, (see
Section 2.22). To set new settings, send the commands
%AANNTTCCFF, (see Section 2.1) and $AAPN, (see
Section 2.23). The new communication settings will be
effective after the next power-on reset.