IMM 8001/8002 – Digital Motor Protection Relay
ICE / CEE
__________________________________________________________________________________________________________________________________________
IMU307-1 GB Ind. B
76
DISPLAY OF PROTECTION AGAINST LOSSES OF LOAD ANSI code [37P/I]
PARAMETER SETTING
→
←
STATISTICS
→
←
PARAMETERS
TABLE 1
→
←
PARAMETERS
TABLE 2
→
←
→
←
VOLTAGES
27 59
→
←
LOSS OF LOAD
37
→
←
↑
↓
37P<
1
OFF-- -- -- --
→
←
Operating level
1
P<
0.1 Sn
→
←
Time-delay
1
tP<
3.0 s
→
←
Inhibit. Time 1
tP<on
30 s
or
37I<
1
OFF -- -- -- --
→
←
Operating level
1
I<
0.15 In
→
←
Time-delay
1
tI<
3.0 s
→
←
Inhibit. Time 1
tI<on
30 s
RANGES
P<
I<
37 – P<
1
OFF -- -- -- --
RANGE : ON / OFF
-- -- -- -- / T P A B
37 – I< 1
OFF -- -- -- --
RANGE : ON / OFF
-- -- -- -- / T P A B
Operating level
1
P<
0.1 Sn
RANGE : 0.1 to 0.5 Sn
STEP : 0.01 Sn
Operating level 1
I<
0.15 In
RANGE : 0.15 to 0.70 In
STEP : 0.01In
Time-delay
1
tP<
3.0 s
RANGE : 1 to 100 s
STEP : 0.1 s
Time-delay
1
TI<
3.0 s
RANGE : 1 to 100 s
STEP : 0.1 s
Inhibit. Time
1
tP<on
3.0 s
RANGE : 1 to 1000 s
STEP : 1 s
Inhibit. Time
1
tI<on
3.0 s
RANGE : 1 to 1000 s
STEP : 1s