IMM 8001/8002 – Digital Motor Protection Relay
ICE / CEE
___________________________________________________________________________________________
_
IMU307-1 GB Ind. B
30
4.2.11.
Consultation of last 5 events (alarms, trips, starts)
The last 5
events classified in trips, alarms, or starts can be consulted in the
STATISTICS
item.
The fault time is displayed only for the trips time - delayed.
4.2.12.
Consultation of start related measurements
Information related to the last start can be consulted in the
Present Status/Start Status
item : time
of last start, remaining start authorisation time
Trem
, new start inhibit time
Tinh
, number of
remaining starts
Σ
st
, last start current, advised heating time constant
Tau A
to allow motor starting
without trip.
4.2.13.
Tables of parameters
There are 2 parameter tables (tables 1 and 2). The other parameters are single (Rated values,
communication parameters, … ).
The
table used (table 1 or 2)
can be modified in the
Rated values
item.
The 2 tables can be read and modified at any time. For each parameter of each table, the table
number 1 or 2 appears on top, to the right.
Always check the present table before modifying a parameter.
4.3. REMOTE OPERATOR DIALOGUE - TRACE
The IMM 8000 relays have 2 communication channels :
one, located at the rear (see chapter 3.10.), is used to place the case in a communication
network managed by a PC or another equipment (please consult us). The informations
required to communicate is written in the User’s Manual document
IMM 8000
communication tables
.
one, located at the front (see chapter 3.11.) is used for easier parameter setting operations
with the
PROSETTING
software (please consult us).
In the event of fault or start, a trace of the 3 currents and the voltage is available via the relay rear
communication channel (see User’s Manual document
IMM 8000 communication tables
).