IMM 8001/8002 – Digital Motor Protection Relay
ICE / CEE
___________________________________________________________________________________________
_
IMU307-1 GB Ind. B
25
46 – Ineg >
1
OFF -- -- -- --
n
46 – Ineg >
1
OFF T -- -- -- --
46 – Ineg >
1
ON T -- -- -- --
The cursor is positioned
on the box of the relay
B
Press key
←
3 times to
go to box T.
Press key
↑
Press key
←
once time
to go to box OFF.
Press key
↑
Press the
ENTER
key to validate the modification.
- Modify the operating level value for the negative phase sequence unit Ineg> in the table 1.
Change from 0.25 In to 0.40 In
Operating level 1
Ineg> 0.25 In
Press the
ENTER
key for modification mode entry.
Operating level 1
Ineg> 0.25 In
Operating level 1
Ineg> 0.40 In
Operating level 1
Ineg> 0.40 In
digit 5 (or the last digit) is
grey and blinks
Increment 5 by 5 (step
value) with key
↑
or
Change to digit 2 with key
←
, then increment up to 4
with key
↑
, then decrement
5 down to 0 with key
↓
Press the
ENTER
key to validate the modification.
To return to a lower adjustment value, proceed in the same manner, but with the key
↓
which is
used to decrement.
Note : - The display is automatically locked to the range extreme values,
- The display follows the adjustment step,
-
If you desire to quickly know the range extreme values, increment or decrement the
digit which is most to the left.