IMM 8001/8002 – Digital Motor Protection Relay
ICE / CEE
____________________________________________________________________________________________
IMU307-1 GB Ind. B
88
TESTS : Verification of OVER VOLTAGE protection [59]
CONNECTION
Protection verification
Voltage generator connected to terminals 21-20
No voltage coefficient of correction.
Sequence of operations to be performed
Results to be obtained
The over voltage function is permanently active.
Check of low-set for over voltage unit
Check of operating level U>
Put into service the protection, and route it to a chosen unit.
Note the value of operating level U>
Gradually increase the voltage up to operating level U>
If necessary, check the U31 value on the display during the injection.
Check of time-delay tU>
Preset the voltage to 1.2 times the displayed operating level.
Cut off the injection, then restore it.
Check of high-set for over voltage unit
Check of operating level U>>
Put into service the protection, and route it to a chosen unit.
Note the value of operating level U>>
Gradually increase the voltage up to operating level U>>
If necessary, check the U31 value on the display during the injection.
Check of time-delay tU>>
Preset the voltage to 1.2 times the displayed operating level.
Cut off the injection, then restore it.
the Start Function indicator LED illuminates on
reaching the displayed operating level.
At the end of the set time-delay :
the selected relay must be energised,
the Alarm indicator LED must illuminate,
the alarm message and related informations must be
displayed.
the Start Function indicator LED illuminates on
reaching the displayed operating level.
the Start Function indicator LED illuminates on
reaching 100 % of the displayed operating level.
at the end of the set time-delay :
the selected relay must be energised,
the Internal Trip indicator LED must illuminate,
the fault message and related informations must be
displayed.