MAP 0310: 332 MHz SMP Node Control
004
Intermittent problem may be occurring.
– Please record following:
Node number
Date / Time fault reported
Type of fault reported.
– Check logs to see if this fault has been previously recorded.
Is this a recurring fault?
Yes No
005
This is not a recurring fault.
– Go to “MAP 0570: End of Call” on page 1-357.
006
Reoccurrence of intermittent fault has been detected.
– Treat this fault as a solid failure.
– Go to Step 017 on page 1-179.
007
– From the control workstation node front panel display:
Shutdown and power-off processor node.
Power-on processor node.
Check LCDs for sequence indicating IPL.
Do the LCDs change?
Yes No
008
Node supervisor card not responding to commands.
– Go to “MAP 0110: Supervisor Subsystem” on page 1-10.
009
Processor node is IPLing.
Do LCDs eventually indicate completion of IPL sequence (i.e. blank or “uuu”)?
Yes No
010
Processor node has problem IPLing.
– Go to Step 008 on page 1-88 to continue service.
011
– From node front panel display, click on “TTY” button to open a TTY console.
– From the TTY console:
Select “Advanced Diagnostic Routines”
(Step 011 continues)
1-178
RS/6000 SP MAPs
Содержание RS/6000 SP
Страница 1: ...RS 6000 SP IBM Maintenance Information Volume 2 Maintenance Analysis Procedures GA22 7376 01...
Страница 2: ......
Страница 3: ...RS 6000 SP IBM Maintenance Information Volume 2 Maintenance Analysis Procedures GA22 7376 01...
Страница 8: ...vi RS 6000 SP MAPs...
Страница 10: ...viii RS 6000 SP MAPs...
Страница 16: ...xiv RS 6000 SP MAPs...
Страница 20: ...xviii RS 6000 SP MAPs...
Страница 60: ...MAP 0130 Processor Node Figure 1 7 Thin Node High Level Diagram 1 40 RS 6000 SP MAPs...
Страница 64: ...MAP 0130 Processor Node Figure 1 11 604 or 604e High Node High Level Component Diagram 1 44 RS 6000 SP MAPs...
Страница 196: ...MAP 0300 332 MHz SMP Node Power 064 continued Go to Step 008 on page 1 169 1 176 RS 6000 SP MAPs...
Страница 383: ......
Страница 387: ......