Follow the suggested actions in the order in which they are listed in the Action column until the problem
is solved.
v
See Chapter 3, “Parts listing, System x3755 Type 8877 and 7163,” on page 25 to determine which
components are customer replaceable units (CRU) and which components are field replaceable units
(FRU).
v
If an action step is preceded by “(Trained service technician only),” that step must be performed only by a
trained service technician.
Error code
Description
Action
180-197-000
SCSI ASPI driver not installed.
1. Remove the RAID adapter, if one is installed, and
run the test again.
2. Reseat the SAS hard disk drive backplane
cables.
3. Replace the following components one at a time,
in the order shown, restarting the server each
time:
a. SAS hard disk drive backplane
b. (Trained service technician only) I/O board.
See “Removing the I/O board assembly” on
page 68 and “Replacing the I/O board
assembly” on page 69.
180-361-003
Failed fan LED test.
1. Reseat the fan.
2. Replace the following components one at a time,
in the order shown, restarting the server each
time:
a. Fan
b. (Trained service technician only) Front fan
board.
c. (Trained service technician only) I/O board.
See “Removing the I/O board assembly” on
page 68 and “Replacing the I/O board
assembly” on page 69.
180-xxx-000
Diagnostics LED failure.
Run the diagnostic LED test for the failing LED.
180-xxx-001
Failed front LED panel test.
1. Reseat the operator information panel. See
“Removing the operator information panel
assembly” on page 66 and “Replacing the
operator information panel assembly” on page 67.
2. Replace the following components one at a time,
in the order shown, restarting the server each
time:
a. Operator information panel. See “Removing
the operator information panel assembly” on
page 66 and “Replacing the operator
information panel assembly” on page 67.
b. (Trained service technician only) I/O board.
See “Removing the I/O board assembly” on
page 68 and “Replacing the I/O board
assembly” on page 69.
134
IBM System x3755 Type 8877 and 7163: Problem Determination and Service Guide
Содержание 7163
Страница 1: ...IBM System x3755 Type 8877 and 7163 Problem Determination and Service Guide...
Страница 2: ......
Страница 3: ...IBM System x3755 Type 8877 and 7163 Problem Determination and Service Guide...
Страница 8: ...vi IBM System x3755 Type 8877 and 7163 Problem Determination and Service Guide...
Страница 40: ...24 IBM System x3755 Type 8877 and 7163 Problem Determination and Service Guide...
Страница 52: ...36 IBM System x3755 Type 8877 and 7163 Problem Determination and Service Guide...
Страница 88: ...72 IBM System x3755 Type 8877 and 7163 Problem Determination and Service Guide...
Страница 194: ...178 IBM System x3755 Type 8877 and 7163 Problem Determination and Service Guide...
Страница 204: ...188 IBM System x3755 Type 8877 and 7163 Problem Determination and Service Guide...
Страница 209: ......
Страница 210: ...Part Number 49Y0109 Printed in USA 1P P N 49Y0109...