v
Follow the suggested actions in the order in which they are listed in the Action column until the problem
is solved.
v
See Chapter 3, “Parts listing, System x3755 Type 8877 and 7163,” on page 25 to determine which
components are customer replaceable units (CRU) and which components are field replaceable units
(FRU).
v
If an action step is preceded by “(Trained service technician only),” that step must be performed only by a
trained service technician.
BMC log message
Sensor
number
Sensor
type
Action
Power supply 2 status
Assertion 01 (Power
supply failure) or 03
(Power supply ac loss)
71
08
1. Check the primary voltages to the power supply.
2. Reseat power supply 2.
3. Replace power supply 2.
4. (Trained service technician only) Replace the I/O board, see
“Removing the I/O board assembly” on page 68 and
“Replacing the I/O board assembly” on page 69.
NMI state
80
13
Make sure that the system software is operating correctly and
does not conflict with other software; the system software has
created a software NMI.
Front cable panel detect
83
1B
1. Make sure that the operator panel cable is connected.
2. Replace the operator information panel assembly. See
“Removing the operator information panel assembly” on page
66 and “Replacing the operator information panel assembly”
on page 67.
USB cable detect
84
1B
1. Make sure that the front panel USB cable is connected.
2. Replace the front panel USB cable.
DASD backplane detect
85
1B
1. Make sure that the SAS signal cable is connected.
2. Replace the SAS signal cable.
IDE cable detect
86
1B
1. Make sure that the IDE power cable is connected.
2. Replace the IDE power cable.
Remote Supervisor
Adapter II SlimLine detect
8C
17
1. Make sure that the Remote Supervisor Adapter II SlimLine is
fully seated in the connector. See “Removing the Remote
Supervisor Adapter II SlimLine” on page 58 and “Replacing the
Remote Supervisor Adapter II SlimLine” on page 58.
2. Replace the Remote Supervisor Adapter II SlimLine. See
“Removing the Remote Supervisor Adapter II SlimLine” on
page 58 and “Replacing the Remote Supervisor Adapter II
SlimLine” on page 58.
ABR status
8F
0F
Information only
CPU 1 status
Assertion 01 (Thermal
trip)
90
07
Information only; if the message remains:
1. Make sure that the fans have good airflow and are not
obstructed.
2. Reseat the microprocessor and heat sink.
3. Replace the microprocessor/memory card. See “Removing a
microprocessor/memory card” on page 51 and “Replacing a
microprocessor/memory card” on page 51.
CPU 1 status
Assertion 05
(Configuration error)
90
07
Make sure that the microprocessor/memory card is installed
correctly. See “Removing a microprocessor/memory card” on page
51 and “Replacing a microprocessor/memory card” on page 51.
166
IBM System x3755 Type 8877 and 7163: Problem Determination and Service Guide
Содержание 7163
Страница 1: ...IBM System x3755 Type 8877 and 7163 Problem Determination and Service Guide...
Страница 2: ......
Страница 3: ...IBM System x3755 Type 8877 and 7163 Problem Determination and Service Guide...
Страница 8: ...vi IBM System x3755 Type 8877 and 7163 Problem Determination and Service Guide...
Страница 40: ...24 IBM System x3755 Type 8877 and 7163 Problem Determination and Service Guide...
Страница 52: ...36 IBM System x3755 Type 8877 and 7163 Problem Determination and Service Guide...
Страница 88: ...72 IBM System x3755 Type 8877 and 7163 Problem Determination and Service Guide...
Страница 194: ...178 IBM System x3755 Type 8877 and 7163 Problem Determination and Service Guide...
Страница 204: ...188 IBM System x3755 Type 8877 and 7163 Problem Determination and Service Guide...
Страница 209: ......
Страница 210: ...Part Number 49Y0109 Printed in USA 1P P N 49Y0109...