7.3.3 Replacing the burner
Warning
The IBC heat exchanger has a small amount of combustion chamber insulation
(refractory), which contains ceramic fibers.
When exposed to extremely high temperatures, the ceramic fibers that contain
crystalline silica can be converted into cristobalite, classified as a possible human
carcinogen.
Avoid disturbing or damaging the refractory. If damage occurs, contact the factory for
directions.
Avoid breathing and contact with skin and eyes and follow these precautions:
1. For conditions of frequent use or heavy exposure, respirator protection is
required. Refer to the “NIOSH Guide to the Selection and Use of Particulate
Respirators Certified under 42 CFR 84” for selection and use of respirators
certified by NIOSH.
For the most current information, NIOSH can be contacted at 1-800-356-4676 or
on the web at www.cdc.gov/niosh.
2. Wear long sleeved, loose fitting clothing, gloves and eyes protection.
3. Assure adequate ventilation.
4. Wash with soap and water after contact.
5. Wash potentially contaminated clothes separately from other laundry and rinse
washing machine thoroughly.
6. Discard used insulation in an air tight plastic bag.
NIOSH stated first aid:
Eye contact - Irrigate and wash immediately.
Breathing - Provide fresh air.
1. Turn off the electric power and gas supply to the combi boiler.
2. Remove the front cover, then remove the four top panel Torx screws to remove the top
access panel.
Warning
Wear a suitable protective mask to avoid ingesting particles from the refractory.
3. Remove the electrical connection to the gas valve with a Philips head screwdriver.
94
Section: Service and maintenance
Содержание CX Series
Страница 6: ...Boiler part diagrams CX 150 CX 199 118 Installation Commissioning Report 122 6 Section Contents...
Страница 10: ...Intentionally left empty...
Страница 13: ...Figure 2 Top and bottom view CX 150 CX 199 dimensions Figure 3 Front and side view CX 199 13 CX 199 dimensions...
Страница 70: ...Intentionally left empty...
Страница 84: ...Intentionally left empty...
Страница 102: ...Intentionally left empty...
Страница 114: ...Appendices Wiring diagrams Figure 48 Controller electrical diagram 114 Section Troubleshooting...
Страница 115: ...Figure 49 Internal wiring diagram 115 Wiring diagrams...
Страница 116: ...Figure 50 Sequence of Operation 116 Section Troubleshooting...
Страница 117: ...8 4 Exploded views of the CX 150 CX 199 appliance 117 8 4 Exploded views of the CX 150 CX 199 appliance...
Страница 119: ...119 Boiler part diagrams CX 150 CX 199...