3.13 Gas piping
Note
Due to the precision of modern modulating boilers it is important to pay special
attention to gas pressure regulation.
Important:
Check gas supply pressure to each boiler with a manometer or other high-
quality precision measuring device. Pressure should be monitored before firing the
boiler, during operation throughout the boiler's full modulation range, and after the call
when the regulator is in a "lock-up" condition.
Pay special attention to retrofit situations where existing regulators may have an over-
sized orifice and/or worn seats, causing pressure “creep” and high lock-up pressures.
A high quality regulator will maintain constant pressure above the boiler’s minimum
specification at all firing rates, and will not exceed the boiler’s maximum pressure
rating when locked-up with no load.
3.13.1 Gas pressure
The boilers require a minimum inlet gas supply pressure of 4.0" w.c. for natural gas or propane
during high fire operation. For either fuel, the inlet pressure shall be no greater than 14.0" w.c.
Confirm this pressure range is available with your local gas supplier.
The inlet gas connection to the boiler is ½" NPT (female).
Adequate gas supply piping must be installed with no smaller than ½" Schedule 40 (e.g., Iron
Pipe Size (IPS) and using a 1" w.c. pressure drop, in accordance with the following chart.
Maximum Gas Pipe Length (ft)
Model
½" IPS
¾" IPS
1" IPS
1¼ " IPS
CX 150 (natural gas)
20'
80'
200'
900'
CX 150 (propane)
50'
200'
600'
2,000'
CX 199 (natural gas)
10'
40'
150'
900'
CX 199 (propane)
30'
125'
400'
1,400'
Table 8
Maximum Gas Pipe Length (ft)
64
Section: Installation
Содержание CX Series
Страница 6: ...Boiler part diagrams CX 150 CX 199 118 Installation Commissioning Report 122 6 Section Contents...
Страница 10: ...Intentionally left empty...
Страница 13: ...Figure 2 Top and bottom view CX 150 CX 199 dimensions Figure 3 Front and side view CX 199 13 CX 199 dimensions...
Страница 70: ...Intentionally left empty...
Страница 84: ...Intentionally left empty...
Страница 102: ...Intentionally left empty...
Страница 114: ...Appendices Wiring diagrams Figure 48 Controller electrical diagram 114 Section Troubleshooting...
Страница 115: ...Figure 49 Internal wiring diagram 115 Wiring diagrams...
Страница 116: ...Figure 50 Sequence of Operation 116 Section Troubleshooting...
Страница 117: ...8 4 Exploded views of the CX 150 CX 199 appliance 117 8 4 Exploded views of the CX 150 CX 199 appliance...
Страница 119: ...119 Boiler part diagrams CX 150 CX 199...