Chapter
8 T
roubleshooting
297
Alarm
Code
Alarm
Level
Alarm Name
Cause/Treatment
0C5
Operation
release
Illegal transition command
in control system
Cause
: 1) Change the operation from the vibration suppress
control operation to the normal position control
operation.
2) Change the operation from the normal position
control operation to the vibration suppress control
operation.
Treatment : Change the sequence so the next action is conducted
after confirming the positioning complete signal
(PEND) is turned ON for both cases 1) and 2).
0C8
Overcurrent
Cause
: The output current in the power circuit section is
increased abnormally.
Treatment : This alarm will not be generated in normal operation.
1) Degradation of motor coil insulation
2) Malfunction of components inside controller
can be concerned.
Check if there is deterioration in the insulation by
measuring the phase resistance between the monitor
connection lines U, V and W. The values for the phase
resistance should be almost the same. There is a
concern the insulation is deteriorated if the values are
different in large amount. Please contact IAI.
0CA
Overheated
Cause
: This indicates overheat (75
°
C or more) of the
components inside the controller.
1) Operation is performed with the load condition
exceeding the specified range.
2) High temperature around the controller.
3) A faulty part inside the controller.
Treatment : 1) Revise the operation condition such as decreasing
the acceleration/deceleration speed.
2) Lower the ambient temperature of the controller.
(Note) This error would not normally occur. If it occurs, confirm
there is not 1) or 2) above. If the same error is issued again
even after confirming 1) or 2) is not in the condition, it is
considered to be a malfunction. Please contact IAI.
0CB
Cold start
Current sensor offset
adjustment error
Cause
: An error was found to the sensor in the status check of
the current detection sensor conducted at the
initializing process in the startup.
1) The current detection sensor or any of its
surrounding parts is faulty.
2) The actuator has moved with external force when
the power was turned ON.
Treatment : It is necessary to replace the PCB if it occurs even
after rebooting the power. Please contact IAI.
ME0306-2A
Содержание MSCON
Страница 1: ...MSCON Controller Instruction Manual Second Edition ...
Страница 2: ......
Страница 4: ...ME0306 2A ...
Страница 8: ...ME0306 2A ...
Страница 20: ...12 ME0306 2A ...
Страница 28: ...20 ME0306 2A ...
Страница 46: ...Chapter 1 Specifications Check 38 ME0306 2A ...
Страница 240: ...3 11 Gateway status LED 232 ME0306 2A ...
Страница 246: ...Chapter 4 Vibration Suppress Control Function 238 ME0306 2A ...
Страница 290: ...Chapter 7 Parameter 282 ME0306 2A ...
Страница 310: ...Chapter 8 Troubleshooting 302 ME0306 2A ...
Страница 354: ...Chapter 9 Appendix 346 ME0306 2A ...
Страница 358: ......
Страница 359: ......