3.8 C
ontrol and functions of Input and output signals of Remote I/O Mode
187
Note1 Set the period taken from entering the position number to turning CSTR ON to 6ms or
longer. Because 6ms timer process on the PLC is also entered to the controller,
positioning at another position may occur. Take the PLC scan time into account.
Note2 The completion position No. output is set to 0 during movement of the actuator.
T1
≥
6ms
(Note 1)
PM1 to PM** = 0
(Note 2)
PM1 to PM** = 0
(Note 2)
Operation of actuator
Not turned ON for
miss-pressing
Approach operation
Pressing
operation
Pressing
Completion
Positioning be setting
of coordinate value
Movement by
positioning
width
Stop of
pressing
Command position No.
PC1 to PC**
(PLC
→
MSCON)
Completed position No.
PM1 to PM**
(MSCON
→
PLC)
Start signal CSTR
(PLC
→
MSCON)
Positioning Completion Signal
PEND
(MSCON
→
PLC)
Turned OFF by
turning PEND OFF
Moving Signal MOVE
(MSCON
→
PLC)
ME0306-2A
Содержание MSCON
Страница 1: ...MSCON Controller Instruction Manual Second Edition ...
Страница 2: ......
Страница 4: ...ME0306 2A ...
Страница 8: ...ME0306 2A ...
Страница 20: ...12 ME0306 2A ...
Страница 28: ...20 ME0306 2A ...
Страница 46: ...Chapter 1 Specifications Check 38 ME0306 2A ...
Страница 240: ...3 11 Gateway status LED 232 ME0306 2A ...
Страница 246: ...Chapter 4 Vibration Suppress Control Function 238 ME0306 2A ...
Страница 290: ...Chapter 7 Parameter 282 ME0306 2A ...
Страница 310: ...Chapter 8 Troubleshooting 302 ME0306 2A ...
Страница 354: ...Chapter 9 Appendix 346 ME0306 2A ...
Страница 358: ......
Страница 359: ......