Consolidated Report
Part 1 - Pipe
Description
Start End
Type
Diameter
Length
Elevation
Pipe
Pipe
7
8
UK80G
TS
80 mm
8.00 m
0.00 m
Pipe
8
9
UK80G
TS
65 mm
3.00 m
0.00 m
Pipe
9
10
UK80G
TS
40 mm
4.00 m
0.00 m
Pipe/E2-N1
10
11
UK80G
TS
40 mm
0.10 m
-0.10 m
Pipe
9
12
UK80G
TS
40 mm
4.00 m
0.00 m
Pipe/E2-N2
12
13
UK80G
TS
40 mm
0.10 m
-0.10 m
Pipe
8
14
UK80G
TS
50 mm
3.00 m
0.00 m
Pipe
14
15
UK80G
TS
40 mm
4.00 m
0.00 m
Pipe/E2-N3
15
16
UK80G
TS
40 mm
0.10 m
-0.10 m
Pipe
14
17
UK80G
TS
40 mm
4.00 m
0.00 m
Pipe/E2-N4
17
18
UK80G
TS
40 mm
0.10 m
-0.10 m
Pipe
6
19
UK80G
TS
40 mm
0.42 m
0.00 m
Pipe
19
20
UK80G
TS
40 mm
6.30 m
0.00 m
Pipe/E1-N1
20
21
UK80G
TS
40 mm
0.10 m
-0.10 m
Part 2 - Equivalent Length
Start End
90
45 Thru Side Union Other
Added
Total
0
1
0
0
0
0
0
0.00 m
10.67 m
1
2
0
0
0
0
0 50mmDH&CV
0.00 m
12.74 m
2
3
0
0
2
1
0
0.00 m
6.28 m
3
4
1
0
0
0
0
0.00 m
2.96 m
4
5
1
0
0
0
0
0.00 m
2.96 m
5
6
1
0
0
0
0
0.00 m
4.75 m
Copyright (c) Hughes Associates, Inc. Licensed to: Tyco Fire Suppression and Building Products
Page:
5
10
of
Calculation Date/Time: Sunday, June 29, 2008, 12:24:17 PM
94
APPENDIX B - HUGHES PROGRAM PRINTOUT
FM-200® (UL/FM)
14A-07H
02
2010-03
Содержание FM-200
Страница 100: ...100 APPENDIX C FM 200 DATA SHEET FM 200 Material Safety Data Sheet MSDS 5 PAGES FM 200 UL FM 14A 07H 02 2010 03...
Страница 102: ...3ULQW DWH 102 APPENDIX C FM 200 DATA SHEET FM 200 UL FM 14A 07H 02 2010 03...
Страница 104: ...3ULQW DWH 104 APPENDIX C FM 200 DATA SHEET FM 200 UL FM 14A 07H 02 2010 03...