Calculation
A portable computer is used to collate the data and calculate
the values�� The associated printer provides a detailed hard
copy of the data on site��
Figure - Typical Printout
Leakage Location
If the enclosure fails the test, or if the client requests, an
inspection of the enclosure with the door fan running can
be made�� This makes it possible to locate the source of any
leakage by using cool chemical smoke�� This procedure
also tests the efficiency of any dampers, etc��
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
RETROTEC DISCHARGE SIMULATION VER�� HA5��1
RETENTION TIME PREDICTION MODEL
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
Location:
Hygood�� Test Enclosure
Room Name:
Test House
Testing Company:
HYGOOD LIMITED
Technician:
C Uzzell
Date:
12��12��96
Whole Room Test��
All Outputs are in METRIC Units��
Gas Being Modelled:
FM200
Lbs/Kgs of Agent in Cylinder(s):
17��00
Net Room Volume (m
3
):
30��00
Room Height (m):
3��20
Minimum Protected Height (m)��
2��90
Minimum Retention Time (min):
10��00
Initial Gas Concentration (%):
7��22
Static Pressure @ Discharge:
0��00
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
Equivalent Leakage Area (ELA m²):
0��0050
Hole in Ceiling (m²):
0��0025
Hole in Floor (BCLA m²):
0��0025
This Room PASSES the Test as the Predicted Retention Time is 10��1 minutes for
the agent/air interface to drop below the minimum protected height��
Witnessed By:
X ___________________________________
Software Conforms to 1992 NFPA 12A/2001 TCD Room Integrity Procedure��
Maximum Allowable ELA (m²):
0��005
Interface Height @ 10 minutes:
2��903
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
Page 1 Of 2 Licensed to: MARCRON SAFETY SYSTEMS (UK) LIMITED
Registration # : 207
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
FAN TEST READINGS & DATA
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
Location:
Hygood�� Test Enclosure
Room Name:
Test House
Temperature IN: 20
Temperature OUT: 20
Static Pressure@FanTest:
0
DEPRESSURE PRESSURE
Operator and Gauges Location
OUT
OUT
Room Pressure Gauge Reading
14��0
14��0
Corrected Room Delta P (pa)
-14��0
14��0
Blower Range Config Used
0��1
0��1
Flow Pressure Gauge Reading
45��0
45��0
Corrected Flow Pressure
31��0
45��0
Calculated Air Flow (1s)
13��4
16��2
Temp�� Corrected Flow
13��4
16��2
Leakage Area (m²)
0��0046
0��0055
Average Leakage Area (m²)
0��0050
- - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - -
R M =
1��639
P C =
13��7
A T=
0��003
A L L -
0��002
C 3 =
3��019
C 4=
0��000
G D =
7��260
K 1-
1��8850
A R =
9��374
T=
605��679
P A =
13��7
F A =
0��500
C F =
1��000
K 2=
0��0046
E L =
0��000
TD =
20��000
Page 2 Of 2 Licensed to: MARCRON SAFETY SYSTEMS (UK) LIMITED
Registration # : 207
9
© 2010 Macron Safety Systems (UK) Limited
SECTION 6 - INTEGRITY TESTING
EQUIPMENT:
FM-200® (UL/FM)
PUBLICATION:
14A-07H
ISSUE No.
02
DATE:
2010-03