2
1
-
+
Electrical Actuator - Suppression Diode
The electrical signal from the detection and/or control
equipment is connected in accordance with the wiring
diagram detailed in Figure 56 when all other installations
have been completed��
Figure - Electrical Actuator Wiring Diagram - Suppression
Diode
This Electrical Actuator is fitted with a suppression diode
in parallel to the coil as indicated�� Connect +ve from
control panel to terminal 1 and -ve from control panel
to terminal 2, on plug connector�� End of line monitoring
device (if required) to be fitted on site��
Before this system is put into operation, the removable
solenoid can be checked by firing the system�� To do this,
REMOVE THE ELECTRICAL ACTUATOR from the
valve�� With power to the actuator, the pin should be firmly
in the down position�� Ensure that the electrical actuator is
reset prior to fitting on to the conatainer valve�� FAILURE
TO RESET THE ACTUATOR WILL RESULT IN THE
POTENTIALLY HAZARDOUS DISCHARGE OF THE
CONTAINER��
Electrical Actuator - Bridge Rectifier
The electrical signal from the detection and/or control
equipment is connected in accordance with the wiring
diagram detailed in Figure 57 when all other installations
have been completed��
Figure 7 - Electrical Actuator Wiring Diagram - Bridge
Rectifier
PLUG CONNECTOR
2
3
2
1
1
This Electrical Actuator is fitted with a bridge rectifier
as indicated�� Connect +ve from control panel to either
terminal 1 or 2 with the reverse for the -ve supply from
control panel, on plug connector�� End of line monitoring
device (if required) to be fitted on site��
Before this system is put into operation, the removable
solenoid can be checked by firing the system�� To do this,
REMOVE THE ELECTRICAL ACTUATOR from the
valve�� With power to the actuator, the pin should be firmly
in the down position�� Ensure that the electrical actuator is
reset prior to fitting on to the conatainer valve�� FAILURE
TO RESET THE ACTUATOR WILL RESULT IN THE
POTENTIALLY HAZARDOUS DISCHARGE OF THE
CONTAINER��
0
SECTION 5 - INSTALLATION
FM-200® (UL/FM)
14A-07H
02
2010-03