Manifolds
It may be necessary to manifold agent containers to
provide the required amount of agent for a hazard, or to
make available the proper increments of agent weight for
the protection of multiple hazards��
Whenever containers are manifolded, the following
rules must be observed��
1�� All containers connected to the same manifold or
pipe must be the same size and filled with the same
agent weight, pressure and fill density��
2�� Agent containers must be located in a single row
and spaced according to section��
3�� A connected reserve may be employed in some
circumstances providing a secondary supply of agent��
4�� Flexible discharge hoses and check valves must be
used at each inlet��
Agent Distribution
Distribution piping will be installed only with approved
piping as indicated in Section 5��
Pipe size reductions may be made by using reducing
tees or reducing bushings or reducing couplings��
39
© 2010 Macron Safety Systems (UK) Limited
SECTION 3 - SYSTEM DESIGN
EQUIPMENT:
FM-200® (UL/FM)
PUBLICATION:
14A-07H
ISSUE No.
02
DATE:
2010-03
Содержание FM-200
Страница 100: ...100 APPENDIX C FM 200 DATA SHEET FM 200 Material Safety Data Sheet MSDS 5 PAGES FM 200 UL FM 14A 07H 02 2010 03...
Страница 102: ...3ULQW DWH 102 APPENDIX C FM 200 DATA SHEET FM 200 UL FM 14A 07H 02 2010 03...
Страница 104: ...3ULQW DWH 104 APPENDIX C FM 200 DATA SHEET FM 200 UL FM 14A 07H 02 2010 03...