![Hygood FM-200 Скачать руководство пользователя страница 30](http://html1.mh-extra.com/html/hygood/fm-200/fm-200_installation-manual_2192834030.webp)
Pressure Switch
The pressure switch is activated by pressure from the
agent during discharge and can be used to signal to a
control panel that the system has actually discharged��
The pressure switch latches on operation and has a reset
button�� The pressure switch is supplied with a 1/4” BSPP
x 1/4” NPT male adaptor (Part No�� 309��013��006)��
Figure 29 - Pressure Switch (Part No. 304.20.007)
Figure 2 - Male Elbow (Part No. 309.013.009)
Technical Information
Material:
Brass
Connection:
1/4” BSPP x 1/4” NPT
Max. Working Pressure:
40 bar (27 psi)
Overall Size:
2mm (L) x 2mm (W)
(1.10” (L) x 1.00 (W))
Weight:
0.00 kg (0.11 lbs)
Technical Information
Housing:
Die-cast Aluminium
Pressure Connection:
Nickel Plated Brass
Switch Point:
4 bar Rising ( psi)
Tolerance:
± 0.34 bar (± psi)
IP Rating:
IP
Connection:
1/4” NPT Female
Conduit Thread:
1/2” NPT Female
Max. Working Pressure:
103.4 bar (100 psi)
DC Switch Rating:
1A 24v dc
Installation Environment:
non-corrosive / indoor
Overall Size:
1mm (L) x 101mm (W)
(.0” (L) x 3.9 (W))
Weight:
1.22 kg (2.9 lbs)
Male Elbow
This elbow can be used on the last slave container when
the pressure switch connection is taken from the manifold
or piping networks��
30
SECTION 2 - SYSTEM COMPONENTS
FM-200® (UL/FM)
14A-07H
02
2010-03
Содержание FM-200
Страница 100: ...100 APPENDIX C FM 200 DATA SHEET FM 200 Material Safety Data Sheet MSDS 5 PAGES FM 200 UL FM 14A 07H 02 2010 03...
Страница 102: ...3ULQW DWH 102 APPENDIX C FM 200 DATA SHEET FM 200 UL FM 14A 07H 02 2010 03...