Manual Actuator
The manual actuator can be fitted to the top of the electrical
actuator or directly onto the valve, after first removing the
protective cap��
Caution.
Before attaching the manual actuator to the
electrical actuator or valve, ensure that the firing pin is
retracted and the safety pin is in place (see Figure 58)��
Note.
The actuator must be hand-tight only��
Figure - Manual Actuator Non-Fire Position
Figure 9 - Manual Actuator Location
Figure 1 - Pneumatic Actuator Location
Multiple Container Actuation
Where several containers comprise one system and are
discharged simultaneously, one container is designated as
the ‘master’ container, and the others are ‘slave’ containers��
The master container can be actuated electrically or
manually�� The slave containers are actuated pneumatically
by the action of the master container discharging��
Pneumatic Actuator
Check that the actuating plungers are in the raised position
(see Figure 60)�� Remove the actuation cap from the top of
the valve assembly (see Figure 46) and carefully screw the
pneumatic actuator to the valve on each slave container��
Note.
The actuator must be hand-tight only��
Figure 0 - Pneumatic Actuator Non-Fire Position
4.0 mm (0.17”)
MINIMUM
4.0 mm (0.17”)
MINIMUM
1
© 2010 Macron Safety Systems (UK) Limited
SECTION 5 - INSTALLATION
EQUIPMENT:
FM-200® (UL/FM)
PUBLICATION:
14A-07H
ISSUE No.
02
DATE:
2010-03