![Hygood FM-200 Скачать руководство пользователя страница 73](http://html1.mh-extra.com/html/hygood/fm-200/fm-200_installation-manual_2192834073.webp)
Introduction
This section provides user inspection and maintenance
guidance for FM-200
®
Engineered Systems�� A log book
will be provided to record all inspections, maintenance,
measurements and actions taken�� The continued capability
for effective performance of an FM-200
®
Total Flooding
Fire Suppression System depends on fully adequate
maintenance procedures, with periodic testing�� Reference
NFPA 2001 section 7-1 to 7-6 and ISO 14520-1��
User’s Programme of Inspection
The installer should provide the user with an inspection
programme for the system and components�� The
programme shall include instructions on the action to be
taken in respect of faults�� The user’s inspection programme
is intended to detect faults at an early stage to allow
rectification before the system may have to operate��
A suitable programme is as follows:-
Weekly Check of Hazard Area
Inspect the hazard area against the original layout to
ensure that there have been no changes that might affect
the proper performance of the fire protection system��
Changes might include:
• Contents of area��
• Use of area��
• Air Handling equipment in area��
• Openings in area��
• Floor/ceiling voids��
• Partitioning��
Weekly Check of Containers
Check storage container pressure gauges and ambient
temperature, compare these pressures to the Temperature
Correction Chart to determine temperature corrected
pressure�� If the container corrected pressure shows a loss
of more than 10%, the containers should be removed for
weighing�� All measurements and actions shall be recorded
in the log book��
Weekly Check of System Components
Make a visual inspection of the system components,
distribution piping and nozzles�� Check the immediate
vicinity of all equipment to ensure that no accidental
damage or tampering has occurred��
Weekly General Check
Inspect the hazard area, access routes, container storage
area, floor voids and areas above suspended ceilings
to ensure housekeeping is good and that no refuse has
accumulated�� Ensure that access to the system container
assemblies and local remote controls is unobstructed��
Monthly Check of Notices
Inspect system and protected spaces to ensure that warning
signs, safety precautions and operating instructions are
posted and clearly visible��
Monthly Personnel Training Check
Check that all personnel who may have to operate
the equipment or system are properly trained and are
authorized to do so, and in particular that new employees
have been instructed in its use��
73
© 2010 Macron Safety Systems (UK) Limited
SECTION 8 - MAINTENANCE
EQUIPMENT:
FM-200® (UL/FM)
PUBLICATION:
14A-07H