HYGOOD
SECTION 5 - INSTALLATION
56
FM-200
®
Installation Guide/11100/02.08.05/Issue 3.3
Discharge Pressure Switch continued...
To wire the discharge pressure switch to the control
panel, unscrew and remove the switch cover plate�� Con-
nect to the appropriate terminals on the microswitch or if
supplied with wires, to the coloured wires which are la-
belled as follows:-
Common (C) (violet)
Normally Open (NO) (blue)
Normally Closed (NC) (black)
CAUTION:
The completion of the installation system,
commissioning tests and hand-over may
occur before the area is ready for use�� In
the event of delay between hand-over and
the risk area being available for protection,
then the system must be left in a 'safe' con-
dition to avoid accidental discharge�� The
system must only be made operative once
the area for protection has been completed
and is operational��
Low Pressure Switch
All container valves are 'Factory fitted' with low pres-
sure warning switches�� Voltage input can be applied to
either terminal��
Accessories
Door Notices
Warning notices are required at all exits and entrances
to protected area, ideally mounted on the door�� Plates
may be drilled and screw fixed or attached using suitable
adhesive��
Manual Release Notices
Manual release notices are required at all manual ac-
tuators, remote manual actuators and call points�� Plates
may be drilled and screw fixed or attached using suit-
able adhesive��
Completion Procedures
For ease of reference completion procedures may be
subdivided into the following sections;
•
Pre Checks and Visual Inspections��
•
Final Connections��
•
Hand over Procedures��
Figure 48 - Low Pressure Switch to Control Panel
diagram.
Connections to Pyrochem PCR-100
NOTE: Program output circuit 4 as a supervisory input
circuit. See Pyrochem PCR-100 manual for programming
details.
Connections to Pyrochem FMM-101 or
FMM-1 Module
NOTE: Program the addressable module as supervisory.
See Pyrochem PCR-400 manual for programming details.
NOTE
: When the device (i��e�� pressure switch) is con-
nected to a standard supervisory input circuit, there will
be no distinction between a wiring fault and device ac-
tuation �� This device is to only be utilised when accepted
by the authority having jurisdiction��
HYGOOD
SECTION 5 - INSTALLATION
56
FM-200
®
Installation Guide/11100/02.08.05/Issue 3.3
Discharge Pressure Switch continued...
To wire the discharge pressure switch to the control
panel, unscrew and remove the switch cover plate�� Con-
nect to the appropriate terminals on the microswitch or if
supplied with wires, to the coloured wires which are la-
belled as follows:-
Common (C) (violet)
Normally Open (NO) (blue)
Normally Closed (NC) (black)
CAUTION:
The completion of the installation system,
commissioning tests and hand-over may
occur before the area is ready for use�� In
the event of delay between hand-over and
the risk area being available for protection,
then the system must be left in a 'safe' con-
dition to avoid accidental discharge�� The
system must only be made operative once
the area for protection has been completed
and is operational��
Low Pressure Switch
All container valves are 'Factory fitted' with low pres-
sure warning switches�� Voltage input can be applied to
either terminal��
Accessories
Door Notices
Warning notices are required at all exits and entrances
to protected area, ideally mounted on the door�� Plates
may be drilled and screw fixed or attached using suitable
adhesive��
Manual Release Notices
Manual release notices are required at all manual ac-
tuators, remote manual actuators and call points�� Plates
may be drilled and screw fixed or attached using suit-
able adhesive��
Completion Procedures
For ease of reference completion procedures may be
subdivided into the following sections;
•
Pre Checks and Visual Inspections��
•
Final Connections��
•
Hand over Procedures��
Figure 48 - Low Pressure Switch to Control Panel
diagram.
Connections to Pyrochem PCR-100
NOTE: Program output circuit 4 as a supervisory input
circuit. See Pyrochem PCR-100 manual for programming
details.
Connections to Pyrochem FMM-101 or
FMM-1 Module
NOTE: Program the addressable module as supervisory.
See Pyrochem PCR-400 manual for programming details.
NOTE
: When the device (i��e�� pressure switch) is con-
nected to a standard supervisory input circuit, there will
be no distinction between a wiring fault and device ac-
tuation �� This device is to only be utilised when accepted
by the authority having jurisdiction��
Discharge Pressure Switch (Continued)
To wire the discharge pressure switch to the control panel,
unscrew and remove the switch cover plate�� Connect to
the appropriate terminals on the microswitch or if supplied
with wires, to the coloured wires which are labelled as
follows:-
Common (C) (violet)
Normally Open (NO) (blue)
Normally Closed (NC) (black)
Low Pressure Switch
All container valves are ‘Factory fitted’ with low pressure
warning switches�� Voltage input can be applied to either
terminal��
Figure - Low Pressure Switch to Control Panel diagram.
Connections to Pyrochem PCR-100
NOTE: Program output circuit 4 as a supervisory input circuit.
See Pyrochem PCR-100 manual for programming details.
Connections to Pyrochem FMM-101 or FMM-1 Module
NOTE: Program the addressable module as supervisory. See
Pyrochem PCR-400 manual for programming details.
NOTE:
When the device (i��e�� pressure switch) is
connected to a standard supervisory input circuit, there
will be no distinction between a wiring fault and device
actuation �� This device is to only be utilised when accepted
by the authority having jurisdiction��
Accessories
Door Notices
Warning notices are required at all exits and entrances
to protected area, ideally mounted on the door�� Plates
may be drilled and screw fixed or attached using suitable
adhesive��
Manual Release Notices
Manual release notices are required at all manual
actuators, remote manual actuators and call points�� Plates
may be drilled and screw fixed or attached using suitable
adhesive��
Completion Procedures
For ease of reference completion procedures may be
subdivided into the following sections;
Pre Checks and Visual Inspections��
Final Connections��
Hand over Procedures��
•
•
•
CAUTION:
The completion of the installation system,
commissioning tests and hand-over may occur
before the area is ready for use�� In the event
of delay between hand-over and the risk area
being available for protection, then the system
must be left in a ‘safe’ condition to avoid
accidental discharge�� The system must only be
made operative once the area for protection has
been completed and is operational��
TB2-1
TB2-1
Low Pressure Switch
4.7 K EOL
Resistor
47 K EOL
Resistor
Low Pressure Switch
4
SECTION 5 - INSTALLATION
FM-200® (UL/FM)
14A-07H
02
2010-03
Содержание FM-200
Страница 100: ...100 APPENDIX C FM 200 DATA SHEET FM 200 Material Safety Data Sheet MSDS 5 PAGES FM 200 UL FM 14A 07H 02 2010 03...
Страница 102: ...3ULQW DWH 102 APPENDIX C FM 200 DATA SHEET FM 200 UL FM 14A 07H 02 2010 03...
Страница 104: ...3ULQW DWH 104 APPENDIX C FM 200 DATA SHEET FM 200 UL FM 14A 07H 02 2010 03...