UL: EX4678/EX6077
TFS & BP FM-200 FLOW CALCULATION TEPG3.03b
Project: Example Calculation
File Name: example for UL Design Manual-updated.FLC
Customer Information
Company Name: TFS&BP
Address: Hewett Road
Great Yarmouth
Norfolk, N231 ONN
Phone: 44(0) 1493 417 600
Contact:
Title:
Tim Broughton
Engineering Manager
Project Data
Project Name: Example Calculation
Designer: Tim Broughton
Number:
Account:
Location:
Description:
001
001
Example
Computer Suite
Consolidated Report
Copyright (c) Hughes Associates, Inc. Licensed to: Tyco Fire Suppression and Building Products
Page:
1
10
of
Calculation Date/Time: Sunday, June 29, 2008, 12:24:17 PM
Consolidated Report
Elevation: 0 m (relative to sea level)
Atmospheric Correction Factor: 1
Enclosure Information
Enclosure Number: 1
Name: Switch Room
Enclosure Temperature...
Minimum: 20.0 C
Maximum: 20.0 C
Maximum Concentration: 6.429 %
Design Concentration...
Adjusted: 6.428 %
Minimum:
Minimum Agent Required:
Width:
Length:
Height:
Volume:
Non-permeable:
Total Volume:
Adjusted Agent Required:
Number of Nozzles:
6.400 %
60.4 kg
6.98 m
6.92 m
2.50 m
120.75 cubic m
0.00 cubic m
120.75 cubic m
60.6 kg
1
Copyright (c) Hughes Associates, Inc. Licensed to: Tyco Fire Suppression and Building Products
Page:
2
10
of
Calculation Date/Time: Sunday, June 29, 2008, 12:24:17 PM
91
© 2010 Macron Safety Systems (UK) Limited
APPENDIX B - HUGHES PROGRAM PRINTOUT
EQUIPMENT:
FM-200® (UL/FM)
PUBLICATION:
14A-07H
ISSUE No.
02
DATE:
2010-03
Содержание FM-200
Страница 100: ...100 APPENDIX C FM 200 DATA SHEET FM 200 Material Safety Data Sheet MSDS 5 PAGES FM 200 UL FM 14A 07H 02 2010 03...
Страница 102: ...3ULQW DWH 102 APPENDIX C FM 200 DATA SHEET FM 200 UL FM 14A 07H 02 2010 03...
Страница 104: ...3ULQW DWH 104 APPENDIX C FM 200 DATA SHEET FM 200 UL FM 14A 07H 02 2010 03...