ENS 3000 IO-Link
21
Edition: 2020-04-20
HYDAC
ELECTRONIC
GMBH
Part No.: 669898
12.2 Setting ranges for the switching outputs
Measuring
range/ rod
length
Lower limit of
RP (FL)
Upper limit of
SP (FH)
Minimum
difference betw.
RP and SP
or FL and FH
Increment*
in cm
in cm
in cm
in cm
17.0 / 25.0
0.2
17.0 0.2
0.1
29.0 / 41.0
0.3
29.0 0.3
0.1
39.0 / 52.0
0.4
39.0 0.4
0.1
59.0 / 73.0
0.6
59.0 0.6
0.1
* All ranges shown in the table can be adjusted by the increments shown.
SP = switch point; RP = switch-back point; FL = pressure window lower value;
FH = pressure window upper value
Measuring
range/ rod
length
Lower limit of
RP (FL)
Upper limit of
SP (FH)
Minimum
difference betw.
RP and SP
or FL and FH
Increment*
in inch
in inch
in inch
in inch
6.70 / 9.80
0.1
6.7 0.1 0.05
11.4 / 16.20
0.15
11.4 0.15 0.05
15.35 / 20.50
0.2
15.35 0.2
0.05
23.20 / 28.70
0.25
23.2 0.25 0.05
* All ranges shown in the table can be adjusted by the increments shown.
Measurement
range
Lower limit
of RP (FL)
Upper limit
of SP (FH)
Minimum
difference betw.
RP and SP
or FL and FH
Increment*
-25 .. +100°C
-23.5 °C
100.0 °C
1.5 °C
0.5°C
-13 .. + 212 °F
-10 °F
212 °F
3 °F
1 °F
* All ranges shown in the table can be adjusted by the increments shown.
12.3 Setting ranges for the offset
Rod length
in cm
Measurement
range
in cm
Setting range
Offset in cm *
Increment*
in cm
25 17 0 .. 68
0.1
41 29 0 .. 116
0.1
52 39 0 .. 156
0.1
73 59 0 .. 177
0.1
* All ranges shown in the table can be adjusted by the increments shown.
Rod length
in inch
Measurement
range
in inch
Setting range
Offset in inch *
Increment*
in inch
9.8 6.7 0 .. 26.8
0.05
16.2 11.4 0 .. 45.6
0.05
20.5 15.35 0 .. 61.4
0.05
28.7 23.2 0 .. 69.6
0.05
* All ranges shown in the table can be adjusted by the increments shown.