ENS 3000 IO-Link
27
Edition: 2020-04-20
HYDAC
ELECTRONIC
GMBH
Part No.: 669898
15.2 Changing the Programming Enable
•
In the extended functions menu, please press the key "
" until "PRG" appears.
•
Press the "mode" key.
•
You can choose between free programming "FREE" and locked programming "Loc".
By pressing "
" or “
“ you can switch between these options.
•
Confirm by pressing the "mode" key.
16 Messages
16.1 Error Messages
If an error is detected, a corresponding error message appears which must be
acknowledged by pressing any key.
Possible error messages are as follows:
E.10
A data error has been detected in the saved settings. Possible causes are
strong electromagnetic interference or a defective component.
Action:
Check all the settings (programming enable, switch points, switch-back points
and basic settings) and correct them if necessary. Should an error occur
frequently, please contact HYDAC Service.
E.20
Implausible measured values have been reported from the level sensor over a
longer period.
Action:
Confirm the error message by pressing any key. Should the error message
continue to be displayed, please contact our service department.
E.21
A communication error has been detected within the level sensor.
Action:
Confirm the error message by pressing any key. Should the error message
continue to be displayed, please contact our service department.
E.22
An internal communication error with the temperature sensor (optional) has
been detected.
Action:
Confirm the error message by pressing any key. Should the error message
continue to be displayed, please contact our service department.