12
ENS 3000 IO-Link
Edition: 2020-04-20
HYDAC ELECTRONIC GMBH
Part No.: 669898
7 Commissioning
Caution
Before commissioning, select the type of fluid (default settings: Oil), procedure
see
chapter
13.2
Add-on functions
.
Method of determining the offset value:
We suggest the following procedure for determining the value of the fluid level offset:
Installation resp. mounting of ENS 3000 inside the tank
Check: is the display flashing or does it show a value greater than zero?
If the display is flashing, the level lies outside the active measuring range (level too high,
resp. level too low).
If the system reports low level, the level will gradually be filled up by a fluid until 0 is
displayed. Then, the ENS 3000 is removed from the tank and the fluid level inside the
tank is determined by a measuring unit. Depending on the model, this value is displayed
in the menu in "cm" or "inch" after having been determined .
If the display shows value > 0 or if high level is reported, the level is gradually reduced
by draining the fluid until the value 0 appears in the display. After removing the
ENS 3000 from the tank the procedure is as described above.
Notes:
•
Low fluid level : top up the fluid until a valid measurement is detected.
•
High fluid level : drain the fluid until a valid measurement is detected.
Notes:
•
If the actual fluid level exceeds the upper limit of the unit's nominal range, it can
no longer be measured. The display starts to flash.
The values of the switching outputs and analogue outputs are maintained. The
measured peak fluid level or the pre-set offset is shown in the display.
•
If, after a voltage breakdown, the display shows "..........." (flashing centre LEDs),
it should be checked whether the tank level is too high or too low.
The analogue output provides 4 mA resp. 0 V depending on the setting of the
analogue input.
•
If the actual fluid level falls below the lower limit of the unit's nominal range, it can
no longer be measured and the display will start to flash.
The values of the switching outputs and analogue outputs are maintained. In the
display, 0.0 or. the set offset appears.
ofs