Variable "Primary Value SP1" index=64 id=V_PrimaryValueSp1
data type: 112-bit Record (subindex access not supported)
access rights: rw
modifies other variables
subindex
bit
offset
data type
allowed
values
default
value
mod. other var.
name
description
1
104
8-bit UInteger
0 = Normally
Open, 1 =
Normally
Closed
0
V_Bdc1Behavior
Direction
2
96
8-bit UInteger
2 = Window,
3 = Two-
Point
3
V_Bdc1Behavior
Mode
3
80
16-bit Integer
See 12.2
60
V_Bdc1hresholds Lower Threshold
4
64
16-bit Integer
See 12.2
68
V_Bdc1Thresholds Upper Threshold
5
32
32-bit UInteger
0..9999000
1000
On Delay
6
0
32-bit UInteger
0..9999000
1000
Off Delay
octet
0
1
2
3
4
5
6
7
bit offset
111 - 104
103 - 96
95 - 88
87 - 80
79 - 72
71 - 64
63 - 56
55 - 48
subindex
1
2
3
3
4
4
5
5
element bit
7 - 0
7 - 0
15 - 8
7 - 0
15 - 8
7 - 0
31 - 24
23 - 16
octet
8
9
10
11
12
13
bit offset
47 - 40
39 - 32
31 - 24
23 - 16
15 - 8
7 - 0
subindex
5
5
6
6
6
6
element bit
15 - 8
7 - 0
31 - 24
23 - 16
15 - 8
7 - 0
Die Schaltbits BDCx sowie die physischen Schaltausgänge SPx sind intern
miteinander gekoppelt. Änderungen an den BDCs wirken sich automatisch
auf die SPs aus und umgekehrt. Wenn die IO-Link-Blockparametrierung
verwendet wird, sollten Änderungen an der Schalteinstellung unbedingt an
beiden Ausgangsvariablen (BDC und SP) gleichermaßen vorgenommen
werden.
The switching bits BDCx and the physical switching outputs SPx are
internally coupled. Changes to the BDCs automatically affect the SPs and
vice versa. If the IO-Link block parameterization is used, changes to the
switch setting should be made to both output variables (BDC and SP)