Parameter
Description
Data export
Specifies whether data can be reported.
File format
Format 1, Format 2, Format 3, and Format 4 are
supported.
NOTE
Format 2 has two more information points than Format 1:
E-Day (current-day energy yield) and E-Total (total energy
yield). Format 3 has more information points than Format 1
and Format 2: power meter, PID module, user-defined
device, and SmartLogger data. Format 4 has more
information points than Format 3: active and reactive power
of power meters.
File name
Set this parameter to the format of the file name.
Time format
Set this parameter to the time format.
Export mode
The value can be Cyclic or Fixed time.
● Cyclic: Periodically reports data. Export interval
specifies the period for reporting data. File mode
specifies whether all data or only the incremental
data of a day is reported each time.
● Fixed time: Reports data at a specified time. Fixed
time specifies the time for reporting data.
NO TE
You can click Start report test to check whether the SmartLogger can report data to the FTP
server.
----End
Troubleshooting
NO TICE
If the error code is not listed in the following table, provide SmartLogger run logs
and contact Huawei technical support.
Error Code
Troubleshooting Suggestion
Error Code
Troubleshooting Suggestion
0x1002
Configure the FTP server
address.
0x1003
1. Check whether the DNS
server address is correctly
configured.
2. Check whether the domain
name of the third-party FTP
server is correctly
configured.
SmartLogger3000
User Manual
8 FAQ
Issue 10 (2022-08-20)
Copyright © Huawei Technologies Co., Ltd.
257