Parameter
Description
Address mode
The value can be Comm. Address or Logical address.
If the communications address of the device
connected to the SmartLogger is unique, you are
advised to select Comm. Address. In other cases, you
must select Logical address.
SmartLogger address
Set this parameter to the communications address of
the slave SmartLogger.
Fast scheduling
[1]
The default value is Enable.
● Set this parameter to Enable to enable the fast
scheduling function of the SmartLogger Modbus
TCP interface.
● Set this parameter to Disable to disable the fast
scheduling function of the SmartLogger Modbus
TCP interface.
Note [1]: This parameter can be set only for V300R023C00 and later versions.
The fast scheduling function of the Modbus TCP interface is mutually exclusive
with the GOOSE fast scheduling function. The fast scheduling function of only
one protocol takes effect at a time.
Step 2 Log in to the WebUI of the master SmartLogger, set access parameters for the
slave SmartLogger, and click Add Devices.
Figure 6-40 Setting access parameters
Parameter
Description
Device Type
Set this parameter to SmartLogger.
IP address
Set this parameter to the IP address of
the slave SmartLogger.
----End