Parameter
Description
Remarks
Power derating
caused by
overfrequency
If this parameter is set to Enable, the active power
of the device will be derated according to a certain
slope when the grid frequency exceeds the
frequency that triggers overfrequency derating.
-
Cutoff
frequency of
overfrequency
derating (Hz)
Specifies the frequency threshold for cutting off
overfrequency derating.
● This parameter is
displayed when the
Power derating
caused by
overfrequency is set
to Enable.
● The parameter setting
should meet the
following condition:
Quit frequency of
overfrequency
derating ≤ Trigger
frequency of
overfrequency
derating < Cutoff
frequency of
overfrequency
derating.
Cutoff power of
overfrequency
derating (%)
Specifies the power threshold for cutting off
overfrequency-caused derating.
Trigger
frequency of
overfrequency
derating (Hz)
The standards of certain countries and regions
require that the output active power of devices be
derated when the power grid frequency exceeds a
certain value.
Quit frequency
of
overfrequency
derating (Hz)
Specifies the frequency threshold for exiting
overfrequency derating.
Power drop
gradient of
overfrequency
derating (%/s)
Specifies the decrease rate of the overfrequency
derating power.
Power recovery
gradient of
overfrequency
derating (%/
min)
Specifies the recovery rate of the overfrequency
derating power.
Frequency
detection filter
time (ms)
Specifies the frequency detection filter time.
-
Recovery delay
of frequency-
based active
power derating
Specifies the exiting delay time after the frequency
reaches the quit frequency of overfrequency
derating.
-
Execution delay
of frequency-
based active
power derating
Specifies the effective delay time of overfrequency
derating when the frequency reaches the trigger
frequency of overfrequency derating.
-
Hysteresis of
frequency-
based active
power derating
Specifies whether to enable overfrequency derating
hysteresis.
-
SmartLogger3000
User Manual
6 WebUI Operations
Issue 10 (2022-08-20)
Copyright © Huawei Technologies Co., Ltd.
154