No.
Item
Requirement
15
Corrosive
airborne
contaminant
s
l
The copper corrosion rate is less than 300 Å
b
/month per
ANSI
c
/ISA
d
-71.04-1985 severity level G1.
l
The silver corrosion rate is less than 200 Å/month.
l
You are advised to ask a professional organization to monitor
the corrosive airborne contaminants in the equipment room.
a: ISO (International Organization for Standardization)
b: Å is a unit of length equal to 1/10000000000 (one ten billionth) of a meter.
c: ANSI (American National Standards Institute)
d: ISA (Instrument Society of America)
OceanStor N8500 Clustered NAS Storage System
Installation Guide (for T Series V100R005)
4 Checking the Installation Environment
Issue 02 (2015-09-22)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
31